2011-08-19 15:49:22 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. G1, CODE COMPLIANCE, STATES EXISTING OCCUPANCY AS B. |
| OUR RECORDS SHOW THIS AS A2, SEE FBC 302. A CHANGE OF |
| OCCUPANCY IS TO COMPLY WITH ONE OF THE METHODS IN THE |
| EXISTING BUIDLING CODE. PLEASE NOTE CHANGE OF OCCUPANCY |
| ON THE PLAN AND CONFIRM COMPLIANCE WITH ALL |
| REQUIREMENTS. |
| |
| 2. ACCESSIBLE PARKING TO BE LOCATED ON AN ACCESSIBLE |
| ROUTE NO LESS THAN 44", PLEASE SHOW DIMENSION OF ACCESS |
| AISLE AND ACCESSIBLE ROUTE FBC11-4.6. |
| |
| 3. IT APPEARS THAT DETECTABLE WARNINGS MAY BE REQUIRED |
| FROM THE ACCESSIBLE PARKING TO THE BUILDING AS IT |
| CROSSES THE DRIVE THRU AREA, FBC11-4.25.9. |
| |
| 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR MIAMIDADE |
| NOA REQUIRED FOR ALL COMPONENTS & CLADDING. THE ROOF |
| PRODUCT APPROVAL MAY BE SUBMITTED WITH THE ROOF PERMIT |
| (SEE 11080356). PROVIDE PRODUCT APPROVAL FOR THE |
| FOLLOWING: |
| EXTERIOR DOORS |
| STOREFRONT |
| HARDIPLANK SIDING |
| |
| PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL, FBC106.3.3. |
| |
| 5. A1, 321 B NOTES A MAX 1/2" ELEVATION CHANGE. PLEASE |
| SEE DOOR PRODUCT APPROVAL AND THRESHOLD AND PROVIDE |
| MORE INFORMATION REGARDING HOW THE ELEVATION CHANGE |
| PLUS DOOR THRESHOLD, IF ANY, WILL COMPLY WITH FBC |
| 11-4.3.8 (DOORS 1 & 8). |
| |
| 6. ADVISORY ONLY, SEPARATE PERMIT, PLANS AND REVIEWS |
| WILL BE REQUIRED FOR THE CANOPY. ALTERNATIVELY, SUBMIT |
| ALL STRUCTURAL AND SITE PLAN INFORMATION TO HAVE IT |
| INCLUDED IN THE SCOPE OF WORK FOR THIS PERMIT. |
| |
| 7. THE WATER FOUNTAINS APPEAR TO OBSTRUCT THE |
| MANEUVERING CLEARANCE REQUIRED FOR DOORS 5 & 6, PULL |
| SIDE. PLEASE NOTE THAT A SINGLE FOUNTAIN WITH A CUP |
| HOLDER WOULD BE ACCEPTABLE IF DESIGNER CHOOSES TO ELECT |
| THIS OPTION (FOUNTAIN AT WHEELCHAIR HEIGHT) PER |
| BUILDING OFFICIAL. |
| |
| 8. A9 SHOWS STUCCO TERMINATING BELOW GRADE. SEE |
| FBC1407.3 AND REVISE DETAIL TO SHOW COMPLIANCE. |
| |
| 9. ADDITION AND CANOPY ARE NOT SHOWN ON THE SITE PLAN. |
| PLEASE REVISE. |
| |
| 10. CURB RAMP NOT TO BE LESS THAN 44", FBC 11-4.7.3, |
| PLEASE ADD DIMENSION TO A0. |
| |