Plan Review Notes
Plan Review Notes For Permit 11080357
Permit Number 11080357
Review Stop B
Sequence Number 1
Notes
Date Text
2011-08-19 15:49:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. G1, CODE COMPLIANCE, STATES EXISTING OCCUPANCY AS B.
 OUR RECORDS SHOW THIS AS A2, SEE FBC 302. A CHANGE OF
 OCCUPANCY IS TO COMPLY WITH ONE OF THE METHODS IN THE
 EXISTING BUIDLING CODE. PLEASE NOTE CHANGE OF OCCUPANCY
 ON THE PLAN AND CONFIRM COMPLIANCE WITH ALL
 REQUIREMENTS.
  
 2. ACCESSIBLE PARKING TO BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44", PLEASE SHOW DIMENSION OF ACCESS
 AISLE AND ACCESSIBLE ROUTE FBC11-4.6.
  
 3. IT APPEARS THAT DETECTABLE WARNINGS MAY BE REQUIRED
 FROM THE ACCESSIBLE PARKING TO THE BUILDING AS IT
 CROSSES THE DRIVE THRU AREA, FBC11-4.25.9.
  
 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR MIAMIDADE
 NOA REQUIRED FOR ALL COMPONENTS & CLADDING. THE ROOF
 PRODUCT APPROVAL MAY BE SUBMITTED WITH THE ROOF PERMIT
 (SEE 11080356). PROVIDE PRODUCT APPROVAL FOR THE
 FOLLOWING:
 EXTERIOR DOORS
 STOREFRONT
 HARDIPLANK SIDING
  
 PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL, FBC106.3.3.
  
 5. A1, 321 B NOTES A MAX 1/2" ELEVATION CHANGE. PLEASE
 SEE DOOR PRODUCT APPROVAL AND THRESHOLD AND PROVIDE
 MORE INFORMATION REGARDING HOW THE ELEVATION CHANGE
 PLUS DOOR THRESHOLD, IF ANY, WILL COMPLY WITH FBC
 11-4.3.8 (DOORS 1 & 8).
  
 6. ADVISORY ONLY, SEPARATE PERMIT, PLANS AND REVIEWS
 WILL BE REQUIRED FOR THE CANOPY. ALTERNATIVELY, SUBMIT
 ALL STRUCTURAL AND SITE PLAN INFORMATION TO HAVE IT
 INCLUDED IN THE SCOPE OF WORK FOR THIS PERMIT.
  
 7. THE WATER FOUNTAINS APPEAR TO OBSTRUCT THE
 MANEUVERING CLEARANCE REQUIRED FOR DOORS 5 & 6, PULL
 SIDE. PLEASE NOTE THAT A SINGLE FOUNTAIN WITH A CUP
 HOLDER WOULD BE ACCEPTABLE IF DESIGNER CHOOSES TO ELECT
 THIS OPTION (FOUNTAIN AT WHEELCHAIR HEIGHT) PER
 BUILDING OFFICIAL.
  
 8. A9 SHOWS STUCCO TERMINATING BELOW GRADE. SEE
 FBC1407.3 AND REVISE DETAIL TO SHOW COMPLIANCE.
  
 9. ADDITION AND CANOPY ARE NOT SHOWN ON THE SITE PLAN.
 PLEASE REVISE.
  
 10. CURB RAMP NOT TO BE LESS THAN 44", FBC 11-4.7.3,
 PLEASE ADD DIMENSION TO A0.
  