Plan Review Notes For Permit 11080351 |
Permit Number |
11080351 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-12 14:11:58 | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | 210.12 | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A | | SWITCHED RECEPTACLE OR LIGHT. AT LEAST ONE GFCI | | PROTECTED RECEPTACLE IS REQUIRED AT FRONT AND REAR. NEC | | 210.70 | | PROVIDE A BRANCH CIRCUIT FOR THE BATHROOMS. NEC 210.11 | | (C)(3) | | THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT | | AND A SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70 | | INDICATE THE LOCATION OF THE ELECTRIC SERVICE AND | | PANELBOARD ON THE PLAN. NEC 110.26 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|