2011-08-12 14:11:58REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A
 SWITCHED RECEPTACLE OR LIGHT. AT LEAST ONE GFCI
 PROTECTED RECEPTACLE IS REQUIRED AT FRONT AND REAR. NEC
 210.70
 PROVIDE A BRANCH CIRCUIT FOR THE BATHROOMS. NEC 210.11
 (C)(3)
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND A SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
 INDICATE THE LOCATION OF THE ELECTRIC SERVICE AND
 PANELBOARD ON THE PLAN. NEC 110.26
  