Plan Review Notes
Plan Review Notes For Permit 11080332
Permit Number 11080332
Review Stop Z
Sequence Number 1
Notes
Date Text
2011-08-15 16:25:38AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PER CITY ENGINEERING STANDARDS, THE RESURFACING OF
 PARKING LOTS IS DEFINED AS A THE CONSTRUCTION OF A
 PARKING FACILITY. AS A RESULT, THE FACILITY MUST MEET
 THE PROVISIONS OF THE ZONING CODE. THEREFORE, A SIGNED
 AND SEALED LANDSCAPE PLAN WILL BE REQUIRED FOR THE
 PARKING.
  
 A SEPARATE PERMIT IS REQUIRED FOR LANDSCAPING.
  
 LANDSCAPED TERMINAL ISLANDS MUST BE BUILT TO TERMINATE
 EACH END OF THE PARKING ROW.
  
 A 2' LANDSCAPE BUFFER, INCLUSIVE OF 6" CURBING, MUST BE
 CONSTRUCTED ALONG THE S. DIXIE FRONTAGE IN BETWEEN THE
 INGRESS AND EGRESS DRIVEWAYS FOR THE PROPERTY. THE
 BUFFER SHALL CONSIST EITHER HEDGES OR GROUND COVER
 INSTALLED EVERY 2' ON CENTER.
  
 ALL NEW LANDSCAPING MUST BE IRRIGATED. AN IRRIGATION
 PERMIT WILL BE REQUIRED.
  
 THE SITE PLAN FOR THE PARKING LOT MUST SHOW THE DOUBLE
 STRIPING AND DIMENSIONS FOR EACH PARKING STALL AS WELL
 AS THE DIMENSIONS FOR THE DRIVE AISLES. A WIDTH OF 24'
 IS REQUIRED FOR TWO-WAY DRIVE AISLES.
  
 THE SITE PLAN MUST ALSO SHOW THE LOCATION AND
 DIMENSIONS OF ALL DRIVEWAYS FOR THE LOT.
  
 PLEASE CONSULT SEC 94-485 FOR THE PROVISIONS REGARDING
 STALL PAINTING AND DIMENSIONS AS WELL AS THE
 REQUIREMENTS FOR DISABLED PARKING SPACES.
  
 YOUR RESUBMISSION MAY GENERATE ADDITIONAL COMMENTS.
  
  