2011-08-10 14:37:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE MORE INFORMATION REGARDING OCCUPANCY
 CLASSIFICATION OF THIS STRUCTURE. OUR RECORDS (PRIOR TO
 SUBMITTAL OF A RES REMOD PERMIT SHOWING RENOVATION TO
 EXISTING DWELLING UNIT) SHOW THIS AS BUSINESS
 OCCUPANCY.
  
 2. UNLESS EVIDENCE CAN BE PROVIDED THAT THIS WAS A
 MIXED USE STRUCTURE, SHOW COMPLIANCE WITH FBC11-4.13.8
 (DOOR THRESHOLD HEIGHT LIMITATION).
  
 3. FAC9N-3, PROVIDE FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL FOR THE DOOR. THE EVALUATION REPORT WAS
 SUBMITTED BUT THE COVER SHEET FROM
 WWW.FLORIDABUILDING.ORG IS ALSO REQUIRED.
  
 4. IMPACT PROTECTION REQUIRED, FBC1609.1.4. NON IMPACT
 STOREFRONT PRODUCT APPROVALS WERE SUBMITTED.
  
 5. THE FLOOR PLAN SHOWS HORIZONTAL ROLLER WINDOWS, BUT
 BOTH HORIZONTAL ROLLER AND SINGLE HUNG WINDOW PRODUCT
 APPROVALS WERE SUBMITTED.
  
  