2011-08-12 12:38:174200 NORTH FLAGLER DRIVE - FITNESS BUILDING
 PERMIT #11080116
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: CIVIL SITE DRAWINGS TO BE SUBMITTED AS SEPARATE
 PACKAGE.
  
  
 NO ADDRESS PROVIDED IN TITLEBLOCK.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 DESIGN SHALL CONFORM TO THE 2007 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA EDITION
 OF NFPA 1 AND NFPA 101.
  
 SHEET G101 LIFE SAFETY PLAN NOT SUBMITTED.
  
 NO OCCUPANCY TYPE OR OCCUPANT LOAD INFORMATION
 PROVIDED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 NO FITNESS EQUIPMENT OR FURNITURE PLAN SUBMITTED.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. THE TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 ALL INTERIOR WALL AND CEILING FINISHES SHALL BE CLASS
 A, CLASS B OR CLASS C.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 SHEET A-101: DOOR #125A NOT PROVIDED WITH A FIRE
 RATING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  