2011-08-22 14:53:50FITNESS BUILDING #11080116
 4200 N. FLAGLER DR.
  
 PROVIDE A DEDICATED SPACE WITHIN THE ELECTRICAL
 EQUIPMENT ROOM FOR THE TRANSFORMER AND PANEL BOARDS.
 NEC110. 26 (E)
 GENERAL PURPOSE RECEPTACLES LOCATED OUTDOORS AND IN
 BATHROOMS REQUIRE GFCI PROTECTION. NEC 210.8
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER