Plan Review Notes For Permit 11080115 |
Permit Number |
11080115 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-22 14:26:06 | CAFETERIA BUILDING # 11080115 | | | | GENERAL PURPOSE RECEPTACLES LOCATED AT THE BAR, | | KITCHEN, OUTDOOR AND BATHROOMS REQUIRE GFCI PROTECTION. | | NEC 210.8 | | VERIFY THE OUTDOOR FANS ARE RATED FOR A WET OR DAMP | | LOCATION. NEC 110.11 | | PANELBOARD CB AND CC REQUIRE OVERCURRENT PROTECTION. | | NEC 408.36 | | DRY-TYPE TRANSFORMERS OVER 112 1/2 KVA REQUIRE A | | TRANSFORMER ROOM OF FIRE RESISTANT CONSTRUCTION OR MUST | | BE CONSTRUCTED WITH INSULATION SYSTEM CLASS 155 OR | | HIGHER AND COMPLETELY ENCLOSED OR SEPARATED FROM | | COMBUSTIBLES. | | PROVIDE SAFETY CLEARANCES OF 42 INCHES FROM THE 150K | | TRANSFORMER TO PANEL BOARD CB. IF THE TRANSFORMER IS TO | | BE WALL OR CEILING MOUNTED PLEASE PROVIDE AN ENGINEERED | | MOUNTING DETAIL. NEC TABLE 110.26, 110.13 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|