2011-08-22 14:26:06CAFETERIA BUILDING # 11080115
  
 GENERAL PURPOSE RECEPTACLES LOCATED AT THE BAR,
 KITCHEN, OUTDOOR AND BATHROOMS REQUIRE GFCI PROTECTION.
 NEC 210.8
 VERIFY THE OUTDOOR FANS ARE RATED FOR A WET OR DAMP
 LOCATION. NEC 110.11
 PANELBOARD CB AND CC REQUIRE OVERCURRENT PROTECTION.
 NEC 408.36
 DRY-TYPE TRANSFORMERS OVER 112 1/2 KVA REQUIRE A
 TRANSFORMER ROOM OF FIRE RESISTANT CONSTRUCTION OR MUST
 BE CONSTRUCTED WITH INSULATION SYSTEM CLASS 155 OR
 HIGHER AND COMPLETELY ENCLOSED OR SEPARATED FROM
 COMBUSTIBLES.
 PROVIDE SAFETY CLEARANCES OF 42 INCHES FROM THE 150K
 TRANSFORMER TO PANEL BOARD CB. IF THE TRANSFORMER IS TO
 BE WALL OR CEILING MOUNTED PLEASE PROVIDE AN ENGINEERED
 MOUNTING DETAIL. NEC TABLE 110.26, 110.13
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER