2011-08-05 11:17:064200 NORTH FLAGLER DRIVE - FITNESS CENTER
 PERMIT #11080083
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON DRAWINGS/TITLEBLOCK.
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE - NFPA 1 UNIFORM FIRE CODE.
  
 FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF 18?
 TO THE FRONT, 7?-6? TO THE SIDES AND 4? TO THE BACKSIDE
 PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  