Plan Review Notes For Permit 11080002 |
Permit Number |
11080002 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-17 14:55:57 | 11080002 | | OAKTON PRESERVE TOWNHOMES | | BLDG. 1-5 7 8 | | | | VERIFY THAT ALL NOTES REFLECT THE CURRENT ELECTRIC CODE | | AS BEING THE 2008 NEC. | | PROVIDE A NOTE DEFINING AF FOR THE ELECTRIC PANEL | | DIRECTORY AS MEANING ARC FAULT PROTECTED CIRCUITS. | | CORRECT NOTE ON THE ELECTRICAL LEGEND FOR AFCI TO | | REFLECT THAT ALL GENERAL PURPOSE OUTLETS IN ADDITION TO | | THOSE IN BEDROOMS MUST BE PROTECTED WITH COMBINATION | | AFCI DEVICES. NEC 210.12 | | PROVIDE AN INTERSYSTEM BONDING TERMINATION POINT AT THE | | ELECTRICAL SERVICE LOCATION. NEC 250.94 | | PROVIDE VERIFICATION FROM FPL THAT THE MAXIMUM | | AVAILABLE FAULT CURRENT IS NO MORE THAT 22,000 AIC. NEC | | 110.9 | | A HALL WAY RECEPTACLE IS REQUIRED ON THE SECOND FLOOR | | OF END UNIT #2. NEC 210.52 | | JACUZZI PUMP AND OPTIONAL HEATER (1800 VA) REQUIRE 20 | | AMPERE BRANCH CIRCUITS WITH #12 WIRE NEC 210.19 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|