 OAKTON PRESERVE TOWNHOMES
 BLDG. 1-5 7 8
  
 VERIFY THAT ALL NOTES REFLECT THE CURRENT ELECTRIC CODE
 AS BEING THE 2008 NEC.
 PROVIDE A NOTE DEFINING AF FOR THE ELECTRIC PANEL
 DIRECTORY AS MEANING ARC FAULT PROTECTED CIRCUITS.
 CORRECT NOTE ON THE ELECTRICAL LEGEND FOR AFCI TO
 REFLECT THAT ALL GENERAL PURPOSE OUTLETS IN ADDITION TO
 THOSE IN BEDROOMS MUST BE PROTECTED WITH COMBINATION
 AFCI DEVICES. NEC 210.12
 PROVIDE AN INTERSYSTEM BONDING TERMINATION POINT AT THE
 ELECTRICAL SERVICE LOCATION. NEC 250.94
 PROVIDE VERIFICATION FROM FPL THAT THE MAXIMUM
 AVAILABLE FAULT CURRENT IS NO MORE THAT 22,000 AIC. NEC
 110.9
 A HALL WAY RECEPTACLE IS REQUIRED ON THE SECOND FLOOR
 OF END UNIT #2. NEC 210.52
 JACUZZI PUMP AND OPTIONAL HEATER (1800 VA) REQUIRE 20
 AMPERE BRANCH CIRCUITS WITH #12 WIRE NEC 210.19
  