Date |
Text |
2011-08-17 14:48:43 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) ON THE TITLE SHEET T-1, NOTE #5 UNDER PLUMBING AND |
| THE STRUCTURAL NOTES REFERENCE THE WRONG CODE. PLEASE |
| UPDATE TO THE 2007 FBC W/2009 REVISIONS. |
| |
| 2) ON SHEET OP-1, BOTH THE LARGE AND SMALL PATIO |
| ADDITIONS ARE LABELED ' PATIO OPTION 1'. IN ORDER TO |
| AVOID CONFUSION, PLEASE IDENTIFY EACH AS A DIFFERENT |
| OPTION NUMBER. |
| |
| 3) SPECIFY THE HEIGHT OF THE OPTIONAL ALUMINUM FENCE, |
| THE SPACING OF THE POSTS AND THE SIZE OF CONCRETE |
| ENCASING THE POSTS ON THE PLANS. |
| |
| 4) THE OPENING DESIGN PRESSURES IN THE DOOR AND WINDOW |
| SCHEDULES ON SHEET TU-3.0 DO NOT CORRESPOND WITH THE |
| WIND LOAD TABLES ON THE S-3 SHEETS. PLEASE CORRECT. |
| |
| 5) THE NOA PRESSURES LISTED ON THE PLANS FOR THE XOX |
| HORIZONTAL SLIDING WINDOW IS INCORRECT. THE PRESSURES |
| ARE +/- 75.0 PSF FOR TYPE D, E, F, J, K, L GLASS OR +/- |
| 56.2 FOR TYPE A GLASS, ACCORDING TO THE PRODUCT |
| APPROVAL. PLEASE CORRECT. |
| |
| 6) SUBMIT PRODUCT APPROVALS FOR THE TRUSS ANCHORS AND |
| LINTELS OR A LIST OF ALL TRUSS ANCHORS AND THE LINTELS |
| THAT WILL BE USED WITH THEIR CURRENT PRODUCT APPROVAL |
| NUMBERS. DCA RULE 9N-3 |
| |
| 7) SUBMIT THE CURRENT PRODUCT APPROVALS FOR THE |
| FOLLOWING ITEMS. THE SLIDING GLASS DOOR, THE FIXED |
| WINDOW, THE SINGLE HUNG WINDOW, THE ROOF TILE. DCA RULE |
| 9N-3 |
| |
| 8) SUBMIT THE CURRENT ESR REPORTS FOR THE SELECTION 500 |
| OPEN CELL FOAM INSULATION (ESR 1172) AND THE NO BURN |
| FIRE RESISTANT COATING (ESR 1838), WHICH HAVE BEEN |
| REISSUED. |
| |
| 9) NO TRUSS DRAWINGS OR TRUSS LAYOUT WAS SUBMITTED. IF |
| YOU WOULD LIKE TO HAVE THESE REVIEWED AT THIS TIME, |
| PLEASE SUBMIT THEM. OTHERWISE, A SIGNED AND SEALED SET |
| THAT HAS BEEN REVIEWED AND APPROVED BY THE DESIGNER OF |
| RECORD FOR EACH BUILDING TYPE CAN BE PROVIDED TO THE |
| FIELD INSPECTOR TO BRING IN AND PLACED IN THE RECORDS |
| WITH THE MASTERED PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |