Plan Review Notes For Permit 11070719 |
Permit Number |
11070719 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-03 16:05:31 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. SEE OPENING 2, BOTTOM. TAPCON NOT ALLOWED FOR | | SECTION 6 BOTTOM INTO MASONRY, SEE SHEET 10 OF PRODUCT | | APPROVAL. | | | | 2. SEE SHEET 10 OF PRODUCT APPROVAL. AN EDGE DISTANCE | | OF 3" REQUIRES A .35 FACTOR FOR TAPCONS, .75 FOR SOLID | | SET. THIS FACTOR IS TO BE APPLIED TO THE ANCHOR SPACING | | IN THE ANCHOR SPACING SCHEDULE. | | | | FOR THIS PERMIT ONLY, PER CONVERSATION WITH OWNER, | | CONTRACTOR CAN RESUBMIT REVISED INSTALLATION SCHEDULE | | VIA EMAIL | | |
|