2011-08-05 15:50:53FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 SHEET AM2 :
 1. GREASE INTERCEPTOR REQUIRED
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR
 AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED.
  
 2. PLEASE ADVISE AS TO THE PURPOSE OF THE BOWL SINK IN
 THE FRONT AREA AND THE FLOOR DRAIN IN THE BACK OPEN
 AREA. IF THEY RECEIVE FATS, OILS, OR GREASE THEY ARE
 REQUIRED TO BE CONNECTED TO A GREASE INTERCEPTOR.
  
 3. THE F8 DRAIN SHOWN ON P-1 FOR THE 2C ICE BIN IS NOT
 SHOWN CONNECTED TO THE DRAINAGE ON THE ISO. OR FLAT
 SANITARY DRAWING.
  
 SHEET P-1
  
 4. WATER SUPPLY FOR 3E1 IS NOT SHOWN ON SHEET AM2
  
 NOTE
 1. 608.16.1 BEVERAGE DISPENSERS. THE WATER SUPPLY
 CONNECTION TO BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022, CSA B64.3.1 OR BY AN AIR GAP. THE BACKFLOW
 PREVENTER DEVICE AND THE PIPING DOWNSTREAM THEREFROM
 SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS.
  
 2. SHEET A1 SHOWS AN OLD GREASE TRAP . THIS WILL BE
 REQUIRED TO BE PROPERLY ABANDONED OR INSPECTED FOR
 USABILITY IF USED WITH THE NEW OCCUPANCY.