Plan Review Notes For Permit 11070709 |
Permit Number |
11070709 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-22 07:32:06 | PLANS DENIED | | PROVIDE MODEL NUMBER OF 10 TON RTU ON EQUIPMENT | | SCHEDULE. | | PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO ROOF | | TIE DOWN, | | AND THE UNIT TO CURB TIE DOWN.PER SECTION 301.12 WIND | | RESISTANCE. FBC(M) 2007 | | PROVIDE A DETAIL ON THE CONDENSER STANDS TO ROOF TIE | | DOWN, AND | | UNIT TO STAND TIE DOWN.PER SECTION 301.12 WIND | | RESISTANCE FBC (M) 2007 | | PROVIDE A DETAIL ON THE PLANS FOR THE CONDENSATE | | DISPOSAL FOR THE RTU , COOLER AND FREEZER. | | PER SECTION 307.2 CONDENSATE DISPOSAL.FBC (M) 2007 | | ON PAGE P-1 HAS THE DETAIL FOR THE REMOTE CONDENSER AND | | REFRIGERANT LINES . | | PLEASE MOVE TO THE MECHANICAL PAGES. | | PROVIDE SUBTITLES FOR COOLER AND FREEZER. SECTION | | 106.3.3 2007 FBC. | | PROVIDE WIND LOAD CALCULATIONS FOR WALK IN FREEZER | | 301.12 FBC (M) 2007 | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|