2011-08-11 10:31:09BUILDING PLAN REVIEW
 PERMIT: 11070709
 ADD:7900 S DIXIE
 CONT: MONTEIRO DEVELOPMENT
 TEL: (561)346-6916
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE REVIEW SITE PLAN THE ACCESSIBLE RAMP LOCATED
 ACROSS FROM THE ACCESSIBLE PARKING SPACES. REVIEW
 SECTION: 2007 FBC-B 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM
 OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE. BOTTOM LANDING IS INDICATED AS 5FOOT
 WIDE.
  
 1B) AT THE ACCESSIBLE PARKINGSPACES THE ACCESS AISLE
 DOES INDICATE THE USE OF DETECTABLE SURFACES BUT FROM
 THE BUILDING AT THE BOTTOM OF THE RAMP LANDING NO
 DETECTABLE WARNING
 SURFACES ARE INDICATED. 11-4.29.2.
  
 2A) SHEET A3 INDICATES TTHE USE OF ROOF SCUPPERS AND
 SECONDARY OVER FLOW SCUPPRES BUT NO SIZE IS PROVIDED.
 1504.3.2 & 1504.3.3..
  
 2B) THE UPPER ROOF DOES DUMP THE RAIN WATER ONTO THE
 LOWER ROOF SECTION PLEASE PROVIDE THE TOTAL AREA OF
 BOTH ROOFS IN ROOFING CALCULATION FOR THE LOWER ROOF
 PORTION.1504.3.3
  
 2C) THE RAIN LEADERS ARE NO CLEAR AS TO WHERE THEY STOP
 TO DRAIN ABOVE AND OVER THE SIDE WALK, OR BELOW THE
 SIDE WALK ENDING WHERE? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 3) SHEET A2 DOES INDICATE A NEW COOLER AND EXTERIOR
 FREEZER. COOLERS AND FREEZERS ARE NOT COVERED UNDER
 THIS PERMIT REQUIRING SEPERATE PERMITS PLANS REVIEWS
 AND ASSOCIATED FEES.
 COOLERS AND FREEZERS WILL NEED TO COMPLY WITH 2007
 FBC-B 2603.4.1.2 & 2603.4.1.3. PLEASE BE AWARE THAT
 EXTERIOR FREEZERS AND OR COOLERS WILL ALSO NEED TO
 PROVIDE PRODUCT APPROVALS INDICATING COMPLIANCE WITH
 140 MPH WIND ZONE. RULE 9N-3(31)(G).
  
 4) SHEET P1 INDICATES ROOF TOP REMOTE CONDENSING UNITS
 ATTACHED TO 4X4 WOOD SLEEPRES, PLEASE REVIEW 2007 FBC-B
 SECTION 1509.7 AND TABLE 1509.7.
  
 5) THE PRODUCT APPROVALS SUBMITTED FOR REVIEW (WINDOWS
 & DOORS) ONLY ONE SEET OF APPROVALS WERE SUBMITTED, THE
 BUILDING DEPARTMENT REQUIRES TWO SETS ONE FOR THE FIELD
 AND ONE FOR RECORD RETENTION. 106.3.1.
  
 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIE OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 6A) ROOFING ASSEMBLIES
 6B) PREMANUFACTURED A/C ROOF TOP STANDS
 6C) EXTERIOR FREEZERS-UNDER SEPERATE PERMIT
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  