2011-08-11 10:31:09 | BUILDING PLAN REVIEW |
| PERMIT: 11070709 |
| ADD:7900 S DIXIE |
| CONT: MONTEIRO DEVELOPMENT |
| TEL: (561)346-6916 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1A) PLEASE REVIEW SITE PLAN THE ACCESSIBLE RAMP LOCATED |
| ACROSS FROM THE ACCESSIBLE PARKING SPACES. REVIEW |
| SECTION: 2007 FBC-B 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM |
| OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & |
| LEVEL CLEARANCE. BOTTOM LANDING IS INDICATED AS 5FOOT |
| WIDE. |
| |
| 1B) AT THE ACCESSIBLE PARKINGSPACES THE ACCESS AISLE |
| DOES INDICATE THE USE OF DETECTABLE SURFACES BUT FROM |
| THE BUILDING AT THE BOTTOM OF THE RAMP LANDING NO |
| DETECTABLE WARNING |
| SURFACES ARE INDICATED. 11-4.29.2. |
| |
| 2A) SHEET A3 INDICATES TTHE USE OF ROOF SCUPPERS AND |
| SECONDARY OVER FLOW SCUPPRES BUT NO SIZE IS PROVIDED. |
| 1504.3.2 & 1504.3.3.. |
| |
| 2B) THE UPPER ROOF DOES DUMP THE RAIN WATER ONTO THE |
| LOWER ROOF SECTION PLEASE PROVIDE THE TOTAL AREA OF |
| BOTH ROOFS IN ROOFING CALCULATION FOR THE LOWER ROOF |
| PORTION.1504.3.3 |
| |
| 2C) THE RAIN LEADERS ARE NO CLEAR AS TO WHERE THEY STOP |
| TO DRAIN ABOVE AND OVER THE SIDE WALK, OR BELOW THE |
| SIDE WALK ENDING WHERE? 106.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 3) SHEET A2 DOES INDICATE A NEW COOLER AND EXTERIOR |
| FREEZER. COOLERS AND FREEZERS ARE NOT COVERED UNDER |
| THIS PERMIT REQUIRING SEPERATE PERMITS PLANS REVIEWS |
| AND ASSOCIATED FEES. |
| COOLERS AND FREEZERS WILL NEED TO COMPLY WITH 2007 |
| FBC-B 2603.4.1.2 & 2603.4.1.3. PLEASE BE AWARE THAT |
| EXTERIOR FREEZERS AND OR COOLERS WILL ALSO NEED TO |
| PROVIDE PRODUCT APPROVALS INDICATING COMPLIANCE WITH |
| 140 MPH WIND ZONE. RULE 9N-3(31)(G). |
| |
| 4) SHEET P1 INDICATES ROOF TOP REMOTE CONDENSING UNITS |
| ATTACHED TO 4X4 WOOD SLEEPRES, PLEASE REVIEW 2007 FBC-B |
| SECTION 1509.7 AND TABLE 1509.7. |
| |
| 5) THE PRODUCT APPROVALS SUBMITTED FOR REVIEW (WINDOWS |
| & DOORS) ONLY ONE SEET OF APPROVALS WERE SUBMITTED, THE |
| BUILDING DEPARTMENT REQUIRES TWO SETS ONE FOR THE FIELD |
| AND ONE FOR RECORD RETENTION. 106.3.1. |
| |
| 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIE OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 6A) ROOFING ASSEMBLIES |
| 6B) PREMANUFACTURED A/C ROOF TOP STANDS |
| 6C) EXTERIOR FREEZERS-UNDER SEPERATE PERMIT |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |