2011-08-03 14:40:395101 GREENWOOD AVENUE
 PERMIT #11070640
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE BATTERY CALCULATIONS.
  
 INDICATE IF THE FIRE ALARM SYSTEM IS REQUIRED.
  
 ONLY TWO AUDIBLE DEVICES SHOWN FOR ENTIRE FLOOR PLAN.
 VERFIY THIS IS SUFFICIENT TO MEET THE AUDIBILITY
 REQUIREMENTS OF NFPA 72.
  
 VISUAL NOTIFICATION APPLIANCES NOT PROVIDED IN ALL
 COMMON ROOMS/SPACES SUCH AS RESTROOMS, CONFERENCE
 ROOMS, ETC.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  