Plan Review Notes For Permit 11070631 |
Permit Number |
11070631 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-02 14:02:28 | 3990 NORTH FLAGLER DRIVE | | PERMIT #11070631 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. | | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND | | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION | | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA | | 1). | | | | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS | | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO | | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS | | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED | | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF | | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA | | ADMINISTRATIVE CODE 69A-60.0081. | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | EXIT SIGNS. | | | | INDICATE WHAT COMMODITIES/MATERIALS WILL BE STORED, HOW | | MUCH WILL BE STORED, AND THE STORAGE CONFIGURATIONS. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|