2011-10-11 13:12:29FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 REVIEW COMMENTS FOR #1 WERE NOT ADDERSSED IN THE RESUB
 PACAKGE:
  
 1. SHEET 2P2.1 TECH RESTROOM IS FOR MEN. NO RESTROOM
 FOR WOMEN IS SHOWN.
  
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
  
 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED
 WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS
 SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON
 THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT
 OF EACH SEX, UNLESS STATISTICAL DATA (SUCH AS INDUSTRY
 WIDE STATISTICAL DATA) APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE
 SEXES
  
 2. OK
  
 3. OK
  