Plan Review Notes For Permit 11070618 |
Permit Number |
11070618 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-10-13 14:58:54 | 2301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3 | | PERMIT #11070617 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE A DETAILED SITE PLAN INDICATING FIRE DEPARTMENT | | VEHICLE ACCESS WIDTHS, MARKED FIRE LANES, FIRE HYDRANT | | LOCATIONS, PERIMETER GATES/FENCES, CONSTRUCTION | | TRAILERS ETC. | | | | BUILDING #2: IF POSSIBLE, RELOCATE KNOXBOX AND FIRE | | ALARM ANUNCIATOR PANEL NEAR AN EAST ENTRY DOOR AS THIS | | WILL BE THE ACCESS SIDE FOR EMERGENCY RESPONDERS. THE | | WEST SIDE OF THE BUILDING ABUTTS THE FENCE AND PROPERTY | | LINE. | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE | | FIRE DEPARTMENT AFTER ALL OTHER PLAN REVIEWER COMMENTS | | HAVE BEEN SATISFIED. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|