Plan Review Notes
Plan Review Notes For Permit 11070618
Permit Number 11070618
Review Stop P
Sequence Number 1
Notes
Date Text
2011-08-15 15:08:46FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET 2P2.1 TECH RESTROOM IS FOR MEN. NO RESTROOM
 FOR WOMEN IS SHOWN.
  
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
  
 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED
 WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS
 SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON
 THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT
 OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE
 SEXES
  
 2. SHEET P0.1 DETAIL SHOWS A SCHLER SIT-150-C OIL
 SEPARATOR DETAIL. SHEETS 1P-2.1 & 2P-2.1 CALL FOR A
 SEPARATOR WITH NO COLLECTION TANK.
  
 3. SHEET P7.3 ROOF DRAINS SHOULD BE 8" BASED ON 5"
 RAINFALL AND 1/8" PER FOOT FALL. THE COMBINED SECTION
 LABELED 10,316 SHOULD BE 10"
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  