2011-08-11 09:18:39 | 2301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3 |
| PERMIT #11070617 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| DESIGN SHALL CONFORM TO THE 2007 EDITION OF THE FLORIDA |
| FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA EDITION |
| OF NFPA 1 AND NFPA 101. |
| |
| PROVIDE A DETAILED SITE PLAN INDICATING FIRE DEPARTMENT |
| VEHICLE ACCESS WIDTHS, MARKED FIRE LANES, FIRE HYDRANT |
| LOCATIONS, PERIMETER GATES/FENCES, CONSTRUCTION |
| TRAILERS ETC. |
| |
| ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND DEBRIS TO BE REMOVED FROM THE |
| SITE DAILY. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDINGS DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| PROVIDE BUILDING NUMBER AND BUILDING ADDRESS VISIBLE |
| FROM THE STREET. NUMBERS SHALL BE AT LEAST SIX-INCHES |
| IN HEIGHT AND SHALL CONTRAST THE BACKGROUND (REFERENCE: |
| SECTION 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - |
| NFPA 1). |
| |
| PROVIDE A LIFE SAFETY PLAN CLEARLY INDICATING FIRE |
| RATED WALLS, FIRE RATED DOORS, OCCUPANT LOADS, EXIT |
| SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON |
| PATH OF TRAVEL, FIRE EXTINGUISHERS ETC. |
| |
| THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| OF NFPA 101 FLORIDA EDITION 2006. THE ONLY FIRE RATED |
| SEPARATION APPEARS TO BE THE 2-HOUR FIRE BARRIER |
| SEPARATING THE INTERIOR SERVICE BAYS FROM THE ADJACENT |
| INTERIOR SPACE. |
| |
| THE SERVICE AREAS APPEAR TO BE FUNCTIONING MORE LIKE AN |
| INDUSTRIAL/FACTORY OCCUPANCY THAN A STORAGE OCCUPANCY. |
| |
| INDICATE IF THE SERVICE AREAS AND BODY SHOP AREAS WILL |
| BE FUNCTIONING AS A MAJOR OR MINOR REPAIR GARAGE AS PER |
| SECTION 3.3.165.21.1 OF NFPA 1. |
| |
| NO SMOKING OR OPEN FLAME SIGNS TO BE POSTED IN ALL |
| SERVICE AREAS, BODY SHOPS AND PAINT BOOTH AREAS. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| THE BUSINESS OFFICES (#2101, #2104 ETC.) ARE INDICATED |
| AS BEING LOCATED ON THE MEZZANINE; HOWEVER, THIS SPACE |
| DOES NOT MEET THE DEFINITION OF A MEZZANINE (SECTION |
| 8.6.9 NFPA 101) WHEREBY THE MEZZANINE SPACE IS OPEN TO |
| THE FLOOR BELOW UNLESS THE OCCUPANT LOAD OF THE |
| AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED |
| 10. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| HANDRAILS ARE REQUIRED TO BE INSTALLED ON BOTH SIDES OF |
| STAIRS. |
| |
| SPRAYING OF FLAMMABLE LIQUIDS (PAINT) SHALL CONFORM TO |
| THE REQUIMENTS OF NFPA 33. |
| |
| STORAGE AND HANDLING OF FLAMMABLE LIQUIDS SHALL CONFORM |
| TO THE REQUIREMENTS OF NFPA 30. |
| |
| INDICATE THE QUANTITIES OF FLAMMABLE LIQUIDS TO BE |
| HOUSED IN THE PAINT SHOP AND MIXING ROOM. |
| |
| PAINT SHOP #1304 TO BE PROVIDED WITH TWO EXITS WHEREBY |
| ONE FIRE EVENT WILL NOT RESTRICT ACCESS TO BOTH EXITS. |
| |
| INDICATE THE AREAS THAT WILL BE PROTECTED BY A FIRE |
| SUPPRESSION SYSTEM(S). |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR |
| INSTALLATION OF FIRE SPRINKLERS, FIRE ALARMS, PAINT |
| SPRAY BOOTHS AND ANY OTHER SPECIALTY TRADE. |
| |
| SHEET FA0.1 BOTH FIRE ALARM RISER DIAGRAMS INDICATED AS |
| BUILDING #1. |
| |
| SHEET 1FA2.2 NOT SEALED BY ENGINEER. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |