2011-08-09 15:20:41 | BUILDING PLAN REVIEW |
| PERMIT: 11070618 |
| ADD: 2311 OKEECHOBEE BLVD, BLDG# 1 |
| CONT: NORTH AMERICAN AUTOMOTIVE SERVICES |
| TEL: (630)352-8126 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC |
| SUPPLEMENTS |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) 2007 EXST BLD CODE 601.2 CONFORMANCE. AN EXISTING |
| BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH |
| THAT THE BUILDING BECOMES LESS SAFE OR ENERGY EFFICIENT |
| THAN ITS EXISTING CONDITION. IF IN THE ALTERATION THE |
| CURRENT LEVEL OF SAFETY OR SANITATION IS TO BE REDUCED, |
| THE PORTION ALTERED SHALL CONFORM TO THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING . |
| |
| 1A) SHEET 2-A1.0 THE PLANS APPEAR TO HAVE A OCCUPANCY |
| SEPARATION WALL BETWEEN THE AUTOMOBILE REPAIR GARAGE |
| AND MERCANTILE OCCUPANCY. IT APPEARS TO BE TWO |
| UNPROTECTED OPENINGS IN ROOM 1213 BODY SHOP MANAGERS |
| OFFICE? 2007/09 FBC-B TABLE 715.4. |
| |
| 1B) THE WALL IDENTIFIED BY TAG (N) IS NOT IDENTIFIED ( |
| LOCATED BY ROOM # 1200 A) ON SHEET )-A1.0. THIS SHOULD |
| BE A RATED WALL BEING A OCCUPANCY SEPARATION WALL. |
| 2007/09 FBC-B TABLE 508.3.3. |
| |
| 1C) TECH LOCKER ROOM AND RESTROOM HAS WALL |
| IDENTIFICATION TAGS IDENTIFIED BY (G) A ONE HOUR RATED |
| WALL BUT THE DOORS LEADING INTO THESE ROOMS DO NOT |
| INDICATE ANY FIRE RATING? PLEASE SEE 2007/09 FBC-B |
| TABLE 715.4. |
| |
| 1D) LUNCH ROOM WALLS ARE IDENTIFIED BY WALL TAG (N) |
| PLEASE PROVIDE WHAT WALL TYPE CONSTRUCTION THIS IS? |
| |
| 1E) PLEASE PROVIDE WALL TYPE FOR THE MAIN ELECTRIC ROOM |
| WALLS, THEY ARE NOT IDENTIFIED. |
| |
| 2) SHEET 2-A6.0 INDICATES THE USE OF ? INCH OF RIGID |
| COVER BOARD AND 2 INCHES OF POLYISO INSULATION. THE NOA |
| 10-1018.02 PAGE 4 INDICATES THE INSULATION TO HAVE |
| CURRENT NOA?S. |
| |
| 3) THE ROOFING APPROVAL 07-1018.10 DURO-LAST SINGLE PLY |
| PVC ROOFING SYSTEMS OVER CONCRETE DECKS THIS REPORT HAS |
| SUBSYSTEM AND WILL NEED TO CIRCLE WHICH SUBSYSTEM WILL |
| BE INSTALLED. PLEASE REVIEW THE DESIGN PRESSURES |
| ASSOCIATED WITH EACH SUBSYSTEM AND IF LIMITATION 7 OR |
| LIMITATION 9 ARE APPLICABLE. IF LIMITATION 7 IS |
| INDICATED AND ENHANCED FASTENING IS REQUIRED IN ZONES 2 |
| & 3 PLEASE PROVIDE CALCULATIONS. |
| |
| 4) PLEASE REVIEW WALL SECTIONS SHEET 2-A8.0 & 2A8.1 |
| BOTH INDICATE THE USE OF ? INCH EXTERIOR GRADE PLYWOOD |
| FOR SHEATHING, PLEASE REVIEW: |
| FBC-B |
| |
| 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL |
| BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II |
| CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| REQUIRED. |
| |
| 5) THE ABOVE MENTIONED NOA 07-1018.10 IS FOR PVC ROOF |
| SYSTEMS OVER CONCRETE DECKS. |
| SHEET 2-A8.1 INDICATES NEW TOWER SECTIONS THAT WILL |
| NEED A SEPARATE ROOFING PRODUCT APPROVAL FOR THIS TYPE |
| OF ROOFING APPLICATION. |
| |
| 6) SHEET 2A-8.2 DETAIL 6 INDICATES NEW A NEW CONCRETE |
| LINTEL FOUND ON SHEET 2A-8.3 DETAIL A, THERE IS NO SUCH |
| SHEET LOCATED IN THE PLANS. |
| |
| END OF REVIEW |
| |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |