2012-03-05 12:58:042301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3
 PERMIT #11070617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.1
 PARTS #2109 - OPEN GRATE AREA: STORAGE TO BE MAINTAINED
 AT OR BELOW 12'-0" TOTAL HEIGHT. PAINT STRIPE AROUND
 ROOM TO MARK ELEVATION OF MAXIMUM STORAGE, OTHERWISE
 FIRE SPRINKLERS ARE REQUIRED FOR HIGH-PILED STORAGE.
 SOLID FLOOR AREA: PROVIDE PERMANENT SIGNAGE READING
 STORAGE TO BE MAINTAINED 24" BELOW STRUCTURE.
  
 SHEET 1-A2.0
 PROVIDE MINIMUM CEILING HEIGHT OF 7'-6". SURFACE
 MOUNTED LIGHTING MAY IMPEDE UPON THIS HEADROOM.
  
 SHEET 3-A5.0
 INDICATE WHAT MATERIALS AND QUANTITIES OF MATERIALS
 WILL BE STORED IN DETAIL STORAGE #1311.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW