Plan Review Notes For Permit 11070617 |
Permit Number |
11070617 |
|
Review Stop |
FIRE |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2012-03-05 12:58:04 | 2301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3 | | PERMIT #11070617 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET A1.1 | | PARTS #2109 - OPEN GRATE AREA: STORAGE TO BE MAINTAINED | | AT OR BELOW 12'-0" TOTAL HEIGHT. PAINT STRIPE AROUND | | ROOM TO MARK ELEVATION OF MAXIMUM STORAGE, OTHERWISE | | FIRE SPRINKLERS ARE REQUIRED FOR HIGH-PILED STORAGE. | | SOLID FLOOR AREA: PROVIDE PERMANENT SIGNAGE READING | | STORAGE TO BE MAINTAINED 24" BELOW STRUCTURE. | | | | SHEET 1-A2.0 | | PROVIDE MINIMUM CEILING HEIGHT OF 7'-6". SURFACE | | MOUNTED LIGHTING MAY IMPEDE UPON THIS HEADROOM. | | | | SHEET 3-A5.0 | | INDICATE WHAT MATERIALS AND QUANTITIES OF MATERIALS | | WILL BE STORED IN DETAIL STORAGE #1311. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|