Date |
Text |
2012-03-02 16:30:54 | SEPERATE ROOFING PERMIT REQUIRED SEE UNKNOWNS BELOW |
| IDENTIFIED AS (*******) |
| |
| ROOFING REPORTS SUBMITTED: |
| |
| BERRIDGE MANUFACTURING CO ZEE-LOCK PANEL W/ CONTINUOUS |
| CLIP |
| NOA 10-1018.02 |
| PAGE 5 OF 7 TABLE B FIELD -168.5 PERIMETERS & CORNER |
| -176 PSF |
| |
| |
| JOHN MANVILLE INSULATION BOARD |
| NOA 09-0219.09 |
| SUBSYSTEM OR TRADE NAME OF SYSTEM NOT |
| PROVIDED.************************** |
| |
| |
| DUROLAST SINGLE PLY PVC ROOF SYSTEM OVER CONCRETE DECK |
| NOA 07-1018.10 |
| PAGE 6 OF 14 |
| DECK TYPE 31 |
| SYSTEM A(2) |
| MAX PRESSURE -247.5 LIMITATION #9. |
| |
| DURO-LAST SINGLE PLY PVC ROOF SYSTEM OVER WOOD DECK |
| NOA 07-1018.14 |
| PAGE 6 OF 10 |
| DECK TYPE 1I |
| SYSTEM C: |
| MAXIMUM DESIN PRESSURES 45-60 PSF NOT IDENTIFIED |
| LIMITATION # 7 ********************************** |
| ******************************************************* |
| *************************************** |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS |
| PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). REVISIONS REQUIRE ADDITIONAL REVIEWS WITH |
| ASSOCIATED FEES. |
| |
| 1) SHEET 1-A1.1 INDICATES A NEW MEZZANINE LEVEL AND |
| HIGH RACK STORAGE SYSTEM. THE PLANS DON'T |
| HAVE ANY DETAILS FOR THE STRUCTURAL COMPONENTS FOR |
| EITHER SECTION. A REVISION WILL BE REQUIRED |
| INDICATING CODE COMPLIANCE FOR BOTH OF THE AREAS. |
| |
| |