Plan Review Notes
Plan Review Notes For Permit 11070617
Permit Number 11070617
Review Stop B
Sequence Number 4
Notes
Date Text
2012-03-02 16:30:54SEPERATE ROOFING PERMIT REQUIRED SEE UNKNOWNS BELOW
 IDENTIFIED AS (*******)
  
 ROOFING REPORTS SUBMITTED:
  
 BERRIDGE MANUFACTURING CO ZEE-LOCK PANEL W/ CONTINUOUS
 CLIP
 NOA 10-1018.02
 PAGE 5 OF 7 TABLE B FIELD -168.5 PERIMETERS & CORNER
 -176 PSF
  
  
 JOHN MANVILLE INSULATION BOARD
 NOA 09-0219.09
 SUBSYSTEM OR TRADE NAME OF SYSTEM NOT
 PROVIDED.**************************
  
  
 DUROLAST SINGLE PLY PVC ROOF SYSTEM OVER CONCRETE DECK
 NOA 07-1018.10
 PAGE 6 OF 14
 DECK TYPE 31
 SYSTEM A(2)
 MAX PRESSURE -247.5 LIMITATION #9.
  
 DURO-LAST SINGLE PLY PVC ROOF SYSTEM OVER WOOD DECK
 NOA 07-1018.14
 PAGE 6 OF 10
 DECK TYPE 1I
 SYSTEM C:
 MAXIMUM DESIN PRESSURES 45-60 PSF NOT IDENTIFIED
 LIMITATION # 7 **********************************
 *******************************************************
 ***************************************
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS
 PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S). REVISIONS REQUIRE ADDITIONAL REVIEWS WITH
 ASSOCIATED FEES.
  
 1) SHEET 1-A1.1 INDICATES A NEW MEZZANINE LEVEL AND
 HIGH RACK STORAGE SYSTEM. THE PLANS DON'T
 HAVE ANY DETAILS FOR THE STRUCTURAL COMPONENTS FOR
 EITHER SECTION. A REVISION WILL BE REQUIRED
 INDICATING CODE COMPLIANCE FOR BOTH OF THE AREAS.
  
  