2012-02-07 10:58:262301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3
 PERMIT #11070617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET 1-A1.0
 PARTS #1128 - MEZZANINE STAIRS SHALL BE 36" WIDE
 MINIMUM.
  
 PROVIDE FIRE RATED SEPARATION BETWEEN PARTS (STORAGE)
 AND BUSINESS OCCUPANCY. PROTECT ALL OPENINGS AND
 PENETRATIONS.
 NOTE: THE RATED WALLS AND DOORS DO NOT AGREE BETWEEN
 PLAN SHEETS 1-A1.0 AND 1-A3.0.
  
 SHEET A1.1
 PARTS #2109 - THE MEZZANINE MAY BE REQUIRED TO BE
 LIMITED TO 1/3 OR 1/2 THE AREA OF THE FLOOR BELOW.
  
 SHEET 1-A2.0
 PROVIDE MINIMUM CEILING HEIGHT OF 7'-6". NEED VENDOR
 SHELVING LAYOUT TO COMPARE TO SURFACE MOUNTED CEILING
 LIGHT LOCATIONS.
  
 NEED AN ADDITIONAL EXIT SIGN TO LEAD TO SECONDARY EXIT
 IN PARTS #1128.
  
 CUSTOMER WAITING #1117 HAS EXIT SIGNS ROUTING OCCUPANTS
 TO A MORE HAZARDOUS OCCUPANCY.
  
 SHEET 1-A3.0
 RELOCATE TABLES AND CHAIRS (NEAR TWO SOUTH DOUBLE EXIT
 DOORS) TO KEEP DIRECT UNOBSTRUCTED PATH TO EXITS.
  
 PROVIDE EXIT SIGN FOR PARTS STORAGE EAST EXIT AND MINOR
 REPAIRS AREA NORTH EXIT.
 NOTE: THE RCP EXIT SIGN LOCATIONS DO NOT MATCH ON
 SHEETS 1-A2.0 AND 1-A3.0.
  
 SHEET 1-A3.1
 THE MAXIMUM OCCUPANT LOAD FOR THE BUSINESS MEZZANINE
 NEEDS TO BE SHOWN AS 10 PERSONS, OTHERWISE AN
 ADDITIONAL EXIT IS REQUIRED.
  
 SHEET 3-A5.0
 INDICATE WHAT MATERIALS AND QUANTITIES OF MATERIALS
 WILL BE STORED IN DETAIL STORAGE #1311.
  
 GENERAL
 PROVIDE GUARD RAIL FOR PARTS MEZZANINE.
  
 STORAGE NEEDS TO BE MAINTAINED AT 24" BELOW THE CEILING
 OR STRUCTURE IN THE PARTS MEZZANINE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW