2012-02-06 12:27:36 | 11070617 | | 2310 OKEECHOBEE BLVD. | | NAPLETON BLDG. 1 | | | | THE ELECTRICAL EQUIPMENT ROOM REQUIRES TWO ENTRANCES. | | NEC 110.26(C)(2) | | PROVIDE DEDICATED WORKING SPACE AND SAFETY CLEARANCES | | FOR DISTRIBUTION PANELBOARD 1DPC. NEC 110.26 | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | ROOMS. NEC 110.22, 110.16 | | | | | | ROBERT LECKY | | ELECTRIC PLANS EXAMINER | | [email protected] | | |
|