2011-10-05 11:20:59 | BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 11070617 |
| ADD: 2301 OKEECHOBEE BLVD, BLDG# 1 |
| CONT: NORTH AMERICAN AUTOMOTIVE SERVICES |
| TEL: (630)352-8126 |
| |
| 1A) PARTS MEZZANINE IS TO BE A PRE-ENGINEERED SYSTEM |
| VENDOR INSTALLED, UNDER A SEPARATE PERMIT, REVIEW AND |
| ASSOCIATED FEES. |
| |
| 1B) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. |
| IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPRIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| SQ FT. THE |
| COMPUTATIONS & AFFIDAVIT SHALL BE FILED AS A PERMANENT |
| RECORD OF THE BLDG DEPT. |
| |
| |
| 1C) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & |
| SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. |
| SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. |
| |
| 2) ROOFING APPROVALS: |
| |
| NOA: 07-1018.10 |
| DURO-LAST SINGLE PLY PVC ROOFING SYSTEM OVER CONCRETE |
| DECK, |
| PAGE 5, DECK TYPE 31 CONCRETE DECK INSULATED -217.5 |
| LIMITATION # 9 |
| |
| NOA 09-0219.09 |
| JOHN MANVILLE ROOF INSULATION BOARD |
| ROOF ASSEMBLIES ARE APPROVED UNDER SPECIFIC ROOF |
| COVER?S PRODUCT NOA. |
| |
| NOA 07-1018.14 |
| DURO-LAST SINGLE PLY PVC ROOFING SYSTEM OVER WOOD DECK |
| THE INDIVIDUAL SUB-SYSTEMS ARE NOT IDENTIFIED, ROOFING |
| CONTRACTOR WILL NEED TO |
| IDENTIFY SUB-SYSTEM AND IF LIMITATION # 7 APPLIES THEN |
| ENHANCED FASTENING IN ZONES |
| 2 & 3 WILL NEED TO BE CALCULATED AND PREPARED BY EITHER |
| A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. |
| |
| |
| |