Plan Review Notes For Permit 11070617 |
Permit Number |
11070617 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-15 14:28:34 | FBC PLUMBING 2007 REVIEW #1 | | DENIED: | | | | 1. SHEET P0.1 DETAIL SHOWS A SCHLER SIT-150-C OIL | | SEPARATOR DETAIL. SHEETS 1P-2.1 & 2P-2.1 CALL FOR A | | SEPARATOR WITH NO COLLECTION TANK. | | | | 2. SHEET P7.2 THE SECTION OF PIPE LABELED 6,032 SHOULD | | BE 8" . THE SECTION OF PIPE LABELED 9,880 SHOULD BE 10" | | PIPE BASED ON 1/8" PER FOOT & 5" RAINFALL. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | | | | | | | | | |
|