Plan Review Notes
Plan Review Notes For Permit 11070617
Permit Number 11070617
Review Stop E
Sequence Number 1
Notes
Date Text
2011-08-17 10:44:57 
 BUILDING # 1
 RELOCATE THE MAIN BONDING JUMPER FOR BUILDING #1 TO THE
 MAIN DISCONNECTS. NEC 250.24(B)
 PROVIDE AN EQUIPMENT LAYOUT PLAN FOR THE COMPRESSOR
 ROOM SHOWING THE ELECTRIC CIRCUITRY WITH DISCONNECTS
 AND WORKING CLEARANCES. NEC 110.26, 215.5
 A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE SITE
 LIGHTING. THE PLAN SHOULD INCLUDE PHOTO METRICS, THE
 DESIGN WIND LOAD ENGINEERED FOR THE LIGHT POLES AND AN
 ELECTRIC POWER PLAN.
 A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE CAR WASH
 EQUIPMENT
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
  