2011-08-09 14:35:15BUILDING PLAN REVIEW
 PERMIT: 11070617
 ADD: 2301 OKEECHOBEE BLVD, BLDG# 1
 CONT: NORTH AMERICAN AUTOMOTIVE SERVICES
 TEL: (630)352-8126
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC
 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 EXST BLD CODE 601.2 CONFORMANCE. AN EXISTING
 BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH
 THAT THE BUILDING BECOMES LESS SAFE OR ENERGY EFFICIENT
 THAN ITS EXISTING CONDITION. IF IN THE ALTERATION THE
 CURRENT LEVEL OF SAFETY OR SANITATION IS TO BE REDUCED,
 THE PORTION ALTERED SHALL CONFORM TO THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING .
  
 1A) SHEET 1-A1.0 THE PLANS APPEAR TO HAVE A OCCUPANCY
 SEPARATION WALL BETWEEN THE AUTOMOBILE REPAIR GARAGE
 AND PARTS STORAGE AND THE REPAIR GARAGE AND MERCANTILE
 OCCUPANCY. IT APPEARS TO BE A MASONRY OPENING NOT
 PROTECTED NEXT TO DOOR # 1118?
  
 1B) THE ABOVE MENTIONED OCCUPANCY SEPARATION WALL IS
 THE ONLY OCCUPANCY SEPARATION WALL SHOWN ON THE PLANS,
 THERE WOULD APPEAR A OCCUPANCY SEPARATION WALL WOULD BE
 REQUIRED BETWEEN THE PARTS STORAGE AREA AND THE
 MERCANTILE OCCUPANCY. PLEASE PROVIDE THE FOLLOWING FOR
 A MIXED OCCUPANCY, IF THIS BUILDING IS TO BE CONSIDERED
 SEPARATED (FBC-B 508.3.1.3 OR NON-SEPARATED 508.3.2 OR
 IF MEETING THE REQUIREMENTS FOR ACCESSORY OCCUPANCIES
 508.3.1.
 PLEASE NOTE THAT BOTH THE FIRST FLOOR AND MEZZANINE
 SQUARE FOOT LEVELS ARE TO BE TOTALED TOGETHER FOR TOTAL
 SQ FT FOR THIS FIRE LOAD & OCCUPANCY IT APPEARS THE
 PARTS STORAGE AREA IS WELL OVER THE 10% OF THE TOTAL
 FLOOR AREA .
  
 2) THE SECOND ISSUE WITH THE PARTS STORAGE FIRE AREA
 WHICH INCLUDES APPROX. 4000 SQ FT FIRST FLOOR PLUS 3015
 SQ FT ON THE PARTS MEZZANINE (VENDOR INSTALLED).
  
 2A) THIS IS A STORAGE OCCUPANCY IN A BUILDING TYPE L-B.
 PLEASE REVIEW FBC-B MEZZANINE AREA LIMITATION 505.2
 EXCEPTION# 2. THE AGGREGATE AREA OF MEZZANINES IN
 BUILDINGS AND STRUCTURES OF TYPE I OR II CONSTRUCTION
 SHALL NOT EXCEED ONE-HALF OF THE FLOOR AREA OF THE ROOM
 IN BUILDINGS AND STRUCTURES EQUIPPED THROUGHOUT WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND AN APPROVED EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION
 907.2.12.2.
  
 THE MEZZANINE LEVEL WILL NEED TO BE REDUCED OR IT WILL
 BE REQUIRED TO BE CONSIDERED A SECOND FLOOR AND TO MEET
 ALL BUILDING & MEANS OF EGRESS OF A SECOND FLOOR.
  
 2B) THE COMMENT VENDOR INSTALLED, IS THIS A
 PRE-ENGINEERED SYSTEM? THE LIVE LOADS FOR ANY STORAGE
 AREA ABOVE THE GROUND FLOOR WILL NEED TO BE PROVIDED.
 2007/09 FBC-B T 1607.1
 LIGHT 125 PSF AND HEAVY 250 PSF. PLEASE PROVIDE
 ENGINEERING.
  
 2B)(1) 110.4.2 STORAGE & FACTORY- INDUSTRIAL
 OCCUPANCIES. IT SHALL BE THE RESPONSIBILITY OF THE
 OWNER, AGENT, PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE
 FLOOR LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
  
 2B)(2) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR
 PART OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR
 HAZARDOUS PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED
 ON PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 3) THE OTHER AREA OF CONCERN IS FOUND ON 1-A1.1 A
 BUSINESS MEZZANINE. PLEASE PROVIDE:
  
 3A) THE PLANS INDICATE A WALL TYPE M & N WHICH ARE NOT
 FOUND ON 0-A1.0.
  
 3B) PLEASE PROVIDE THE SQUARE FOOTAGE OF MEZZANINE AND
 THE SQUARE FOOTAGE OF OPEN AREA
 THAT COMMUNICATES WITH THIS AREA. FBC-B 505.2 & 505.4.
 IF THIS IS NOT A TRUE MEZZANINE THEN ISSUES WILL ARISE
 FROM THE OPEN STAIR THAT SERVES THIS AREA.
  
 4) BUSINESS MEZZANINE LEVEL WAS BUILT BEFORE THE ADA &
 FLORIDA ACCESSIBILITY CODE WERE IN ACTED. PLEASE
 PROVIDE COMPLIANCE WITH FBC-B 11-4.1.6(1)(K) III)
  NOTHING IN THIS SECTION SHALL BE CONSTRUED TO RELIEVE
 THE OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM
 THE DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE AND BELOW OCCUPIABLE GRADE LEVEL,
 REGARDLESS OF WHETHER THE CODE REQUIRES AN ELEVATOR TO
 BE INSTALLED IN SUCH BUILDING, STRUCTURE, OR FACILITY,
 EXCEPT FOR: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER, AS PROVIDED IN SECTION 553.509,
 FLORIDA STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES
 MUST, AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3(5) OF THIS
 CODE.
  
 5) SHEET 1-A1.0 DOES INDICATE THE USE OF A LIFT TO GAIN
 ACCESS TO THE RESTROOMS AND RETAIL AREAS, PLEASE
 PROVIDE COMPLIANCE WITH 11-4.1.6(1) (B) IF EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, THEN
 EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 11-4.1.1 TO SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR
 NEW CONSTRUCTION. IF THE APPLICABLE PROVISION FOR NEW
 CONSTRUCTION REQUIRES THAT AN ELEMENT, SPACE, OR COMMON
 AREA BE ON AN ACCESSIBLE ROUTE, THE ALTERED ELEMENT,
 SPACE, OR COMMON AREA IS NOT REQUIRED TO BE ON AN
 ACCESSIBLE ROUTE EXCEPT AS PROVIDED IN SECTION
 11-4.1.6(2), ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION. PLEASE PROVIDE MANUFACTURERS
 SPECIFICATIONS.
  
 6) SHEET 1-A1.0 SERVICE AREA AND NEW FIVE FOOT WIDE
 CURB RAMP WILL NEED TO COMPLY WITH FBC-B 11-4.29
 DETECTABLE WARNINGS.
  
 7) SHEET 1-A8.1 DETAILS A & 1AND SHEET 1-A8.2 BOTH
 INDICATE THE USE OF ? INCH EXTERIOR GRADE PLYWOOD FOR
 SHEATHING, PLEASE REVIEW:
 FBC-B
  
 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL
 BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II
 CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN
 ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 7) PLEASE SEE SHEET 1-A8.3 DETAIL A INDICATES THE USE
 OF ? INCH OF RIGID COVER BOARD AND 2 INCHES OF POLYISO
 INSULATION. THE NOA 10-1018.02 PAGE 4 INDICATES THE
 INSULATION TO HAVE CURRENT NOA?S.
  
 8) THE ROOFING APPROVAL 07-1018.10 DURO-LAST SINGLE PLY
 PVC ROOFING SYSTEMS OVER CONCRETE DECKS THIS REPORT HAS
 SUBSYSTEM AND WILL NEED TO CIRCLE WHICH SUBSYSTEM WILL
 BE INSTALLED. PLEASE REVIEW THE DESIGN PRESSURES
 ASSOCIATED WITH EACH SUBSYSTEM AND IF LIMITATION 7 OR
 LIMITATION 9 ARE APPLICABLE. IF LIMITATION 7 IS
 INDICATED AND ENHANCED FASTENING IS REQUIRED IN ZONES 2
 & 3 PLEASE PROVIDE CALCULATIONS.
  
 9) THE ABOVE MENTIONED NOA 07-1018.10 IS FOR PVC ROOF
 SYSTEMS OVER CONCRETE DECKS.
 SHEET 1-A8.2 INDICATES NEW TOWER SECTIONS THAT WILL
 NEED A SEPARATE ROOFING PRODUCT APPROVAL FOR THIS TYPE
 OF ROOFING APPLICATION.
  
 10) DEPENDING ON THE SHEATHING FROM COMMENT #7 THE
 REYNOLDS REYNOBOND COMPOSITE PANEL NOA 10-1118.05 MAY
 NEED AN ENGINEERS ANALYSIS FOR THE TYPE OF SHEATHING TO
 BE INSTALLED SINCE THE PRESSURES ASSOCIATED WITH THIS
 REPORT ARE FROM 5/8 INCH PLYWOOD SHEATHING.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved