Plan Review Notes
Plan Review Notes For Permit 11070562
Permit Number 11070562
Review Stop B
Sequence Number 2
Notes
Date Text
2011-08-03 15:54:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR
 EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE
 CHANGED EFFECTIVE MARCH 1, 2009. RESUB SHEET STATES
 THAT PRESSURES WERE CHANGED. PRESSURES ARE TOO LOW,
 MINIMUM -46.2 FOR ZONE 4.
  
 2. SEE OPENING C, 123 1/4" SPAN STATED. THIS DOES NOT
 CORRELATE WITH THE HEIGHT. IF THIS IS THE SPAN, SEE
 SHEET 11 OF THE PRODUCT APPROVAL. 5" SPACING REQUIRED.
  
 3. TIM ELLIS HAS SIGNED THE PERMIT APPLICATION WHERE
 THE QUALIFIER'S SIGNATURE SHOULD BE. IT IS NOT CLEAR
 WHY THIS PERSON HAS REPRESENTED HIMSELF AS THE
 QUALIFIER. PROVIDE A NEW PROPERLY NOTARIZED PERMIT
 APPLICATION, NO WHITE OUT PERMITTED IN THE NOTARIZED
 SIGNATURE AREA.
  
 4. PRIOR TO RESUBMITTAL, HAVE THE QUALIFIER REVIEW THE
 INSTALLATION SCHEDULE AND PROPOSED DESIGN PRESSURES FOR
 CODE COMPLIANCE.
  
  
  
  
  
  