Plan Review Notes
Plan Review Notes For Permit 11070562
Permit Number 11070562
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-26 10:24:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PRESSURES TO EXPOSURE C OR PROVIDE ENGINEERED
 RATIONAL ANALYSIS FOR USE OF REDUCED PRESSURES, SEE
 ASCE7-05 AND FBC R301.2.1.4.
  
 2. SEE SHEET 11 OF THE PRODUCT APPROVAL. 9" SPACING
 DOES NOT COMPLY. PLEASE ALSO CLARIFY WHICH TAPCON IS
 PROPOSED. INSTALLATION SCHEDULE SPECIFIES "ITW TAPCON"
 BUT SHEET 11 HAS TWO, ITW TAPCON 1/4" AND ITW BULIDEX
 5/8".
  
  