Plan Review Notes
Plan Review Notes For Permit 11070543
Permit Number 11070543
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-07-22 16:36:581 NORTH CLEMATIS STREET, 4TH FLOOR
 PERMIT #11070543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS AND HYDRAULIC CALCULATIONS INDICATE A REMOTE AREA
 OF 1500 SQUARE FEET BUT ONLY SEVEN SPRINKLERS AND
 ROUGHLY 800 SQUARE FEET HAVE BEEN HYDRAULICALLY
 CALCULATED.
  
 PER NFPA 13 THE HYDRAULIC AREA SHALL BE MEASURED
 PARALLEL TO THE BRANCH LINES.
  
 HYDRAULIC CALCULATIONS DO NOT ACCOUNT FOR THE
 ADDITIONAL FRICTION LOSS ASSOCIATED WITH THE FLEXIBLE
 DROPS SUPPLYING SPRINKLERS.
  
 INDICATE ON THE PLANS THE MAXIMUM LENGTH OF FLEXIBLE
 DROPS TO BE USED, THE MINIMUM BENDING RADIUS AND THE
 MAXIMUM NUMBER OF BENDS PERMITTED PER THE LISTING
 REQUIREMENTS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, THE HARD PIPED
 SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT.
 INDICATE THE METHOD FOR RESTRAINING UPWARD MOVEMENT AND
 ADJUST PIPE HANGER LOCATION SCHEDULE AND ARMOVER DETAIL
 FOR 100 PSI.
  
 THE REQUIRED RESIDUAL PRESSURE SHOWN ON THE PLANS IS A
 NEGATIVE NUMBER.
  
 PROVIDE A FLOOR DESIGNATION IN THE TITLE BLOCK OR ON
 THE PLANS.
  
 NOTE: ONLY THE BRAIDED FLEXIBLE HOSE ASSEMBLIES ARE
 ACCEPTED BY THE OFFICE OF THE FIRE MARSHAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW