Plan Review Notes For Permit 11070543 |
Permit Number |
11070543 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-07-22 16:36:58 | 1 NORTH CLEMATIS STREET, 4TH FLOOR | | PERMIT #11070543 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PLANS AND HYDRAULIC CALCULATIONS INDICATE A REMOTE AREA | | OF 1500 SQUARE FEET BUT ONLY SEVEN SPRINKLERS AND | | ROUGHLY 800 SQUARE FEET HAVE BEEN HYDRAULICALLY | | CALCULATED. | | | | PER NFPA 13 THE HYDRAULIC AREA SHALL BE MEASURED | | PARALLEL TO THE BRANCH LINES. | | | | HYDRAULIC CALCULATIONS DO NOT ACCOUNT FOR THE | | ADDITIONAL FRICTION LOSS ASSOCIATED WITH THE FLEXIBLE | | DROPS SUPPLYING SPRINKLERS. | | | | INDICATE ON THE PLANS THE MAXIMUM LENGTH OF FLEXIBLE | | DROPS TO BE USED, THE MINIMUM BENDING RADIUS AND THE | | MAXIMUM NUMBER OF BENDS PERMITTED PER THE LISTING | | REQUIREMENTS. | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, THE HARD PIPED | | SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT. | | INDICATE THE METHOD FOR RESTRAINING UPWARD MOVEMENT AND | | ADJUST PIPE HANGER LOCATION SCHEDULE AND ARMOVER DETAIL | | FOR 100 PSI. | | | | THE REQUIRED RESIDUAL PRESSURE SHOWN ON THE PLANS IS A | | NEGATIVE NUMBER. | | | | PROVIDE A FLOOR DESIGNATION IN THE TITLE BLOCK OR ON | | THE PLANS. | | | | NOTE: ONLY THE BRAIDED FLEXIBLE HOSE ASSEMBLIES ARE | | ACCEPTED BY THE OFFICE OF THE FIRE MARSHAL. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|