Plan Review Notes
Plan Review Notes For Permit 11070530
Permit Number 11070530
Review Stop B
Sequence Number 2
Notes
Date Text
2011-08-02 13:50:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DESIGN PRESSURE OF -46.3 REQUIRES USE OF THE -57
 ROW, SEE SHEET 7 OF THE PRODUCT APPROVAL. C3 REQUIRES
 4.6" SPACING ON ALL OPENINGS OVER 6' AT THE BOTTOM, NOT
 ONLY OPENING 1. IT IS NOT CLEAR WHY OPENING 1 WAS
 CHANGED BUT NOT THE OTHER OPENINGS.
  
 2. AS PREVIOUSLY DISCUSSED, THE PRODUCT APPROVAL IS
 HIGHLIGHTED FOR A DESIGN PRESSURE OF -73PSF. IF YOU ARE
 NOT DESIGNING TO -73PSF, PLEASE SUBMIT TWO NEW PRODUCT
 APPROVALS. TWO COMPLETE SETS OF PLANS FOR PERMIT
 ISSUANCE REQUIRED.
  
  
  
  
  