2011-08-04 09:40:05BUILDING PLAN REVIEW
 PERMIT: 11070370
 ADD: 420 COLUMBIA # 111
 CONT: AUTOBUILDERS
 TEL: (561)622-3515
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW COVER SHEET CODE RESEARCH MEANS OF
 EGRESS WITH TRAVEL LESS THAN 75'-0". SHEET A-1.0 PLEASE
 TAKE THE TRAVEL DISTANCE FROM ONE FOOT OFF OF THE
 NORTH-EAST CORNER OF THE LOUNGE WALL, STAY 1'-0" OFF OF
 WALLS FOR TRAVEL DISTANCE UNTIL YOU REACH THE FRONT
 DOORS, THE LEAST AMOUNT OF TRAVEL DISTANCE THAT I
 MEASURED IS APPROXIMATELY 78'. IF YOU CAN ILLUSTRATE
 YOUR TRAVEL DISTANCE LESS THAN 75'-0" THEN ONLY ONE
 MEANS OF EGRESS IS REQUIRED. IT APPEARS THAT THE LOUNGE
 DOOR LEADING TO THE EXTERIOR (DOOR 107A) WILL BE
 REQUIRED AS A SECOND EXIT SINCE THIS IS A UNSPRINKERED
 BUILDING THE 100 FOOT EXCEPTION CAN NOT BE APPLIED.
 2007/09 FBC-B 1014.3, SEE COMMENTARY WHERE YOU CAN NOT
 TAKE DIAGONAL ROUTES ACROSS ROOMS. THE REASONING IS IF
 THE BUILDING IS FILLED WITH SMOKE YOU WILL NEED TO
 TOUCH THE WALLS TO FIND YOUR WAY TO AN EXIT, IF
 FURNITURE IS IN THE WAY YOU WILL ALSO NEED TO GO AROUND
 SUCH OBSTRUCTIONS.
  
 2) PLEASE REVIEW SHEET A-2.0 DETAILS 1 & 2 RECEPTION
 DESK MUSST MEET TTHE REQUIREMENTS OF 11-7.2 SERVICE
 COUNTERS AND OR INFORMATION COUNTERS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  