2011-08-04 09:40:05 | BUILDING PLAN REVIEW |
| PERMIT: 11070370 |
| ADD: 420 COLUMBIA # 111 |
| CONT: AUTOBUILDERS |
| TEL: (561)622-3515 |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLEASE REVIEW COVER SHEET CODE RESEARCH MEANS OF |
| EGRESS WITH TRAVEL LESS THAN 75'-0". SHEET A-1.0 PLEASE |
| TAKE THE TRAVEL DISTANCE FROM ONE FOOT OFF OF THE |
| NORTH-EAST CORNER OF THE LOUNGE WALL, STAY 1'-0" OFF OF |
| WALLS FOR TRAVEL DISTANCE UNTIL YOU REACH THE FRONT |
| DOORS, THE LEAST AMOUNT OF TRAVEL DISTANCE THAT I |
| MEASURED IS APPROXIMATELY 78'. IF YOU CAN ILLUSTRATE |
| YOUR TRAVEL DISTANCE LESS THAN 75'-0" THEN ONLY ONE |
| MEANS OF EGRESS IS REQUIRED. IT APPEARS THAT THE LOUNGE |
| DOOR LEADING TO THE EXTERIOR (DOOR 107A) WILL BE |
| REQUIRED AS A SECOND EXIT SINCE THIS IS A UNSPRINKERED |
| BUILDING THE 100 FOOT EXCEPTION CAN NOT BE APPLIED. |
| 2007/09 FBC-B 1014.3, SEE COMMENTARY WHERE YOU CAN NOT |
| TAKE DIAGONAL ROUTES ACROSS ROOMS. THE REASONING IS IF |
| THE BUILDING IS FILLED WITH SMOKE YOU WILL NEED TO |
| TOUCH THE WALLS TO FIND YOUR WAY TO AN EXIT, IF |
| FURNITURE IS IN THE WAY YOU WILL ALSO NEED TO GO AROUND |
| SUCH OBSTRUCTIONS. |
| |
| 2) PLEASE REVIEW SHEET A-2.0 DETAILS 1 & 2 RECEPTION |
| DESK MUSST MEET TTHE REQUIREMENTS OF 11-7.2 SERVICE |
| COUNTERS AND OR INFORMATION COUNTERS. |