Plan Review Notes
Plan Review Notes For Permit 11070343
Permit Number 11070343
Review Stop M
Sequence Number 2
Notes
Date Text
2011-11-01 11:33:57REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PREVIOUS REVIEW COMMENT NOT ADDRESSED.
  
 THIS IS A PROPOSED CHANGE OF OCCUPANCY. NO INFORMATION
 WAS PROVIDED REGARDING EXISTING OR PROPOSED NEW
 VENTILATION SYSTEM. SHOW HOW THE VENTILATION
 REQUIREMENTS FOR THE NEW OCCUPANCY ARE TO BE PROVIDED
 IN ACCORDANCE WITH FBC-EB SECTION 909.1 AND FBC-M
 SECTION 403. IF THE VENTILATION REQUIREMENTS FOR THE
 NEW OCCUPANCY ARE LESS OR EQUAL TO THE PREVIOUS
 OCCUPANCY, PROVIDE AN ANLYSIS BASED ON THE REQUIREMENTS
 OF FBC-M SECTION 403.
  