Date |
Text |
2011-07-20 14:17:28 | 1011 NORTH DIXIE HIGHWAY |
| PERMIT #11070343 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION |
| WITH FLORIDA AMENDMENTS. |
| |
| PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANT LOADS, |
| FIRE RATED WALLS, EXIT SIGNS, EMERGENCY LIGHTING, |
| TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. |
| |
| THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| OF NFPA 101 FLORIDA EDITION 2006. INDICATE THE ADJACENT |
| OCCUPANCY TYPES. |
| |
| INDICATE THE EGRESS ROUTES FOR THE ADJACENT TENANT |
| SPACES THAT SHARE THE SECOND FLOOR. |
| |
| INDICATE ON THE PLANS IF THE REAR PATIO AND REAR STAIR |
| ARE ENCLOSED OR OPEN. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| 2 INCHES. |
| |
| THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| EDITION 2007. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| 1). |
| |
| STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| ADMINISTRATIVE CODE 69A-60.0081. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| INDICATE IF THE EXISTING FIRE SPRINKLER OR EXISTING |
| FIRE ALARM SYSTEM IS BEING UTILIZED IN THIS SPACE. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |