Plan Review Notes For Permit 11070343 |
Permit Number |
11070343 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-07-18 14:54:09 | ELECTRICAL PLAN REQUIRED. PLEASE PROVIDE THE FOLLOWING: | | | | INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE | | EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD. | | PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE | | AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING | | LOADS. SHOW NEW AND EXISTING ELECTRICAL OUTLETS. NEC | | 215.5 | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. | | FBC 13-415 ABC.1.2. SPACE CONTROL; 13412.ABC.1.3 | | ADDITIONAL CONTROLS | | SHOW EXIT SIGNS AND EMERGENCY LIGHTING. FBC 1006 | | SHOW GFCI PROTECTION ON APPROPRIATE OUTLETS. NEC 210.8 | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|