Plan Review Notes
Plan Review Notes For Permit 11070343
Permit Number 11070343
Review Stop E
Sequence Number 1
Notes
Date Text
2011-07-18 14:54:09ELECTRICAL PLAN REQUIRED. PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE
 EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD.
 PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE
 AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING
 LOADS. SHOW NEW AND EXISTING ELECTRICAL OUTLETS. NEC
 215.5
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC 13-415 ABC.1.2. SPACE CONTROL; 13412.ABC.1.3
 ADDITIONAL CONTROLS
 SHOW EXIT SIGNS AND EMERGENCY LIGHTING. FBC 1006
 SHOW GFCI PROTECTION ON APPROPRIATE OUTLETS. NEC 210.8
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  