Plan Review Notes
Plan Review Notes For Permit 11070343
Permit Number 11070343
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-18 16:32:02BUILDING PLAN REVIEW
 PERMIT: 11070343
 ADD: 1015 N DIXIE HWY
 CONT: LS INVESTMENTS
 TEL: (561) 282-5692
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES A CHANGE OF USE
 FROM ROOMING HOUSE(R-1 TRANSIENT OR R-2 NON-TRANSIENT)
 TO A BUSINESS OCCUPANCY. THE ONE SHEET PROVIDED IS
 CONCEPTUAL IN NATURE, 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
 106.3.5
 COMMERCIAL BUILDINGS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 FIRE SPRINKLERS
 TENANT SEPERATION WALLS
  
 2) CHANGE OF OCCUPANCY FOR A PORTION OF A BUILDING
 SHALL COMPLY WITH 2007/09 EXISTING BUILDING CODE
 CHAPTER 9, SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 1. THE DESIGNER OF RECORD WILL NEED TO DETERMINE IF
 THIS BUILDING HAS CHANGE OF OCCUPANCY CLASSIFICATION
 WITH OR WITHOUT SEPERATION. 2007 EXST BLD 912.1.1.1/
 912.1.1.2
  
 2. 912.1.2 FIRE PROTECTION AND INTERIOR FINISH.
  
 3. 912.1.4 ACCESSIBILITY SHALL COMPLY WITH EXT BLD
 912.8. PLEASE ALSO REVIEW 2007 FBC-B 11-4.3.11 AREA OF
 RESCUE ASSISTANCE.
  
 4. EXT BLD 912.2.1 FIRE SPRINKLER SYSTEMS
  
 5. EXT BLD 912.2.2 FIRE ALARM & DETECTION
  
 6) EXT BLD 912.3 INTERIOR FINISHES
  
 7) 912.4.2 MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL
 OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD
 CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4,
 EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 EXCEPTION: ANY STAIRWAY REPLACING AN EXISTING STAIRWAY
 WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE
 REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL BE
 PERMITTED FOR CONTINUED USE SUBJECT TO APPROVAL OF THE
 BUILDING CODE OFFICIAL. ALSO, SEE SECTION 1001.4 OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
 912.4.3 EGRESS CAPACITY. EGRESS CAPACITY SHALL MEET OR
 EXCEED THE OCCUPANT LOAD AS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY.
  
 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH
 THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA
 OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH THE
 REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 912.7 ENCLOSURE OF VERTICAL SHAFTS. ENCLOSURE OF
 VERTICAL SHAFTS SHALL BE IN ACCORDANCE WITH SECTIONS
 912.7.1 THROUGH 912.7.4.
  
 912.7.1 MINIMUM REQUIREMENTS. VERTICAL SHAFTS SHALL BE
 DESIGNED TO MEET THE FLORIDA BUILDING CODE, BUILDING
 REQUIREMENTS FOR ATRIUMS OR THE REQUIREMENTS OF THIS
 SECTION.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
  
  
  
  