2012-01-09 16:45:32 | RESIDENTIAL (R2) REPAIRS THIRD BUILDING REVIEW |
| COMMENTS. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- ENGINEER DRAWINGS SUBMITTED ARE ONLY FOR CONDO UNIT |
| #1 OF BUILDING A. THERE ARE 8 DIFFERENT PERMIT |
| APPLICATIONS FOR WORK TO BE PERFORMED ON 8 DIFFERENT |
| CONDO UNITS. PLEASE PROVIDE DRAWINGS IDENTIFYING THE |
| SCOPE OF WORK TO BE PERFORMED ON EACH UNIT. REVISE ALL |
| THE INFORMATION ON PLANS AS REQUIRED. SEC. 106.1.1 CITY |
| AMENDMENTS TO FBC. |
| |
| *** SAME DRAWINGS WERE SUBMITTED WITHOUT IDENTIFYING |
| ALL UNITS INVOLVED IN THESE REPAIRS. |
| |
| 2- PLEASE REVISE THE BUILDING CODE INFORMATION SHOWN ON |
| SHEET C-1: THE OCCUPANCY GROUP IS R2 NOT R3. REVISE AS |
| REQUIRED. |
| |
| *** ENGINEER NEEDS TO REVISE ORIGINAL DRAWINGS. PLANS |
| SUBMITTED ARE THE SAME ONES THAT WERE SUBMITTED ON |
| PREVIOUS REVIEW. THEY HAVE HAND WRITTEN REVISIONS NOT |
| DONE BY THE ENGINEER RESPONSIBLE FOR THE PLANS. ALSO, |
| PLANS SUBMITTED ARE MISSING THE ENGINEER'S SEAL AND THE |
| SIGNATURE MUST BE ORIGINAL NOT COPY. CHAPTER 471 |
| FLORIDA STATUTE. |
| |
| 3- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE |
| BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION |
| AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING, |
| WATERPROOFING, ETC. SEC. 106.1.1 CITY AMENDMENTS TO |
| FBC. |
| |
| *** ENGINEER OF RECORD DIDN'T PROVIDE ANY DRAWINGS. |
| |
| 4- PLEASE PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR |
| THE BALCONY GUARDRAIL TO BE REPLACED TO SHOW COMPLIANCE |
| WITH SEC. 1013 AND SEC. 1607.7 FBC 2007. |
| |
| ***ENGINEER OF RECORD DIDN'T PROVIDE ANY DRAIWGNS |
| |
| 5- ENTRY DOOR NOA 08-1015.05 SUBMITTED DOESN'T MATCH |
| NOA 07--0618.10 SPECIFIED BY THE ENGINEER ON SHEET A-2. |
| REVISE AS REQUIRED TO MATCH. |
| |
| *** ENGINEER DIDIN'T REVISE PLANS. |
| |
| 6- NOTICE OF COMMENCEMENT SIGNATURE WAS CLARIFIED. |
| |
| 7- PLEASE UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK |
| SHOWN ON PLANS. INCLUDE THE DOORS/WINDOWS REPLACEMENT, |
| NEW DECK AND GUARDRAIL AND PROFESSIONAL ENGINEER FEES |
| AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC. |
| PERMIT TYPE AND FEES TO BE ADJUSTED ACCORDINGLY. |
| |
| *** VALUATION WAS NOT UPDATED. |
| |