2011-07-20 17:05:01 | RESIDENTIAL (R2) WINDOW/DOOR REPLACEMENT BUILDING |
| REVIEW CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- MISSING PLANS SPECIFIED ON THE PERMIT APPLICATION. |
| PROVIDE PLANS SHOWING THE WINDOWS AND DOORS TO BE |
| REPLACED AND THE DETAILS/SPECIFICATIONS FOR FRAME |
| SUPPORT STRUCTURAL REPAIRS. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC. |
| |
| 2- SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS |
| AND TYPE AND SIZE OF NEW WINDOWS TO VERIFY COMPLIANCE |
| WITH THE EMERGENCY EGRESS REQUIREMENTS. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| |
| A) HORIZONTAL ROLLING WINDOW. NOA 09-0105.02 SUBMITTED |
| WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE |
| WEBSITE AND DOWNLOAD CURRENT NOA. |
| |
| B) SLIDING GLASS DOOR. NOA 09-0324.16 SUBMITTED WAS |
| SUPERSEDED ALSO BY MIAMI-DADE. NEED CURRENT NOA. |
| |
| C) FIXED WINDOW. NOA 10-0930.04 SUBMITTED IS FOR |
| NON-IMPACT GLASS. NEED TO PROVIDE GLASS PROTECTION AS |
| REQUIRED BY SEC. 1609.1.2 FBC. PROVIDE NOA WITH IMPACT |
| GLASS OR PROVIDE INFORMATION FOR SHUTTERS. |
| |
| D) HURRICANE SHUTTERS IF FIXED WINDOW HAS NO IMPACT |
| GLASS. IN ADDITION PROVIDE COMPLETE SHUTTERS |
| INSTALLATION SCHEDULE AND MARK ON SHUTTERS DRAWINGS |
| SPECIFIC MOUNTING CONDITION (EX: WALL MOUNTED) AND |
| ANCHOR TYPE AND SPACING TO BE USED. SEE CITY POLICY FOR |
| SHUTTERS INSTALLATION. |
| |
| 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| |