2011-07-19 15:41:361009 NORTH DIXIE HIGHWAY
 PERMIT #11070279
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO NFPA 101 LIFE SAFETY CODE
 FLORIDA 2006 EDITION. THE FLOOR PLAN SHOWS MIXED USE OF
 THE OCCUPANCIES BUT VERY LIMITED INFORMATION IS
 PROVIDED FOR THE AREA AROUND THE THEATER SPACE.
  
 THIS SPACE APPEARS TO BE A CHANGE OF OCCUPANCY FROM
 MERCANTILE TO ASSEMBLY. PROVIDE A LIFE SAFETY PLAN
 SHOWING ALL OCCUPANT LOADS, FIRE RATED WALLS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 STORAGE AREAS ARE REQUIRED TO BE SEPARATED FROM THE
 ASSEMBLY AREA WITH A ONE-HOUR FIRE RATED WALL OR SHALL
 BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
  
 INDICATE HOW THE THEATER SPACE IS SEGREGATED FROM THE
 LOBBY SPACE.
  
 SHOW ALL PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2006.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  