2011-07-20 14:29:11 | BUILDING PLAN REVIEW |
| PERMIT: 11070279 |
| ADD: 1009 N DIXIE HWY. |
| CONT: TO BE DETERMINED |
| CONTACT: BOB CARTER |
| TEL: (561)301-2588 CELL |
| 833-7529 BUS. |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) A CONTRACTOR EITHER CGC OR CBC MUST SIGN ON TO THE |
| PERMIT APPLICATION AND TAKE RESPONSIBILITY FOR THE |
| PERMIT. |
| |
| 2) PLEASE VERIFY WHICH OF THE ADDRESSES ARE CORRECT THE |
| PERMIT APPLICATION OR THE PLANS. DISCREPANCY. |
| |
| 3) THE DESIGNER OF RECORD WILL NEED TO DECIDE IF THIS |
| PROJECT IS TO BE DESIGNED AS A MIXED USE BUILDING USING |
| THE NON-SEPERATION METHOD OR SEPERATION METHOD: |
| |
| NONSEPARATED OCCUPANCIES: |
| 508.3.2 NONSEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS |
| OF BUILDINGS THAT COMPLY WITH THE PROVISIONS OF THIS |
| SECTION SHALL QUALIFY AS NONSEPARATED OCCUPANCIES. |
| |
| 508.3.2.1 OCCUPANCY CLASSIFICATION. NONSEPARATED |
| OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN |
| ACCORDANCE WITH SECTION 302.1. CODE REQUIREMENTS SHALL |
| APPLY TO EACH PORTION OF THE BUILDING BASED ON THE |
| OCCUPANCY CLASSIFICATION OF THAT SPACE EXCEPT THAT THE |
| MOST RESTRICTIVE APPLICABLE PROVISIONS OF SECTION 403 |
| AND CHAPTER 9 SHALL APPLY TO THE ENTIRE BUILDING OR |
| PORTION THEREOF. |
| |
| 508.3.2.2 ALLOWABLE AREA AND HEIGHT. THE ALLOWABLE AREA |
| AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE |
| BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE |
| OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF |
| CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION |
| 503.1. |
| |
| 508.3.2.3 SEPARATION. NO SEPARATION IS REQUIRED BETWEEN |
| OCCUPANCIES. |
| |
| EXCEPTION: GROUP H-2, H-3, H-4 OR H-5 OCCUPANCIES SHALL |
| BE SEPARATED FROM ALL OTHER OCCUPANCIES IN ACCORDANCE |
| WITH SECTION 508.3.3. |
| |
| |
| OR |
| |
| 2007/09 FBC-B 508.3.3 SEPERATION |
| 508.3.3 SEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS OF |
| BUILDINGS THAT COMPLY WITH THE PROVISIONS OF THIS |
| SECTION SHALL QUALIFY AS SEPARATED OCCUPANCIES. |
| |
| 508.3.3.1 OCCUPANCY CLASSIFICATION. SEPARATED |
| OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN |
| ACCORDANCE WITH SECTION 302.1. EACH FIRE AREA SHALL |
| COMPLY WITH THIS CODE BASED ON THE OCCUPANCY |
| CLASSIFICATION OF THAT PORTION OF THE BUILDING. |
| |
| 508.3.3.2 ALLOWABLE AREA. IN EACH STORY, THE BUILDING |
| AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS OF THE |
| ACTUAL FLOOR AREA OF EACH OCCUPANCY DIVIDED BY THE |
| ALLOWABLE AREA OF EACH OCCUPANCY SHALL NOT EXCEED ONE. |
| |
| 508.3.3.3 ALLOWABLE HEIGHT. EACH OCCUPANCY SHALL COMPLY |
| WITH THE HEIGHT LIMITATIONS BASED ON THE TYPE OF |
| CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION |
| 503.1. THE HEIGHT, IN BOTH FEET AND STORIES, OF EACH |
| FIRE AREA SHALL BE MEASURED FROM GRADE PLANE. THIS |
| MEASUREMENT SHALL INCLUDE THE HEIGHT, IN BOTH FEET AND |
| STORIES, OF INTERVENING FIRE AREAS. |
| |
| EXCEPTION: SPECIAL PROVISIONS PERMITTED BY SECTION 509. |
| |
| 508.3.3.4 SEPARATION. INDIVIDUAL OCCUPANCIES SHALL BE |
| SEPARATED FROM ADJACENT OCCUPANCIES IN ACCORDANCE WITH |
| TABLE 508.3.3. |
| |
| |
| IF THTE DESIGNER OF RECORD DECIDES TO USE THE |
| NON-SEPERATED METHOD THE FOLLOWING WILL NEED TO BE |
| DEMONSTRATED. |
| STEP 1. DETERMINE WHICH OCCUPANCY GROUPS |
| CLASSIFICATIONS ARE IN THE BUILDING. |
| |
| STEP 2. DETERMINE THE MINIMUM BUILDING TYPE OF |
| CONSTRUCTION BASED ON THE HEIGHT & AREA OF THE BUILDING |
| FOR EACH OCCUPANCY GROUP IN ACCORDANCE WITH THIS |
| CHAPTER AND TABLE 503. APPLY THE REQUIREMENTS FOR THE |
| MOST STRINGENT TO THE ENTIRE BUILDING. |
| |
| STEP 3. APPLY THE MOST RESTRICTIVE PROVISIONS CONTAINED |
| IN SECTION 403 ( NOT APPLICABLE) AND CHAPTER 9 |
| THROUGHOUT ALL NONSEPARATED USES (SECTION 508.3.2.1). |
| |
| STEP 4. APPLY ALL OTHER REQUIREMENTS OF THE CODE TO |
| EACH OCCUPANCY INDIVIDUALLY BASED ON THE SPECIFIC |
| OCCUPANCY OF EACH SPACE( E.G. MEANS OF EGRESS) (SECTION |
| 508.3.2.1). |
| |
| 4) ELEVATED PLATFORMS SHALL COMPLY WITH: |
| 4A) 1003.5 ELEVATION CHANGE. CHANGE IN LEVEL IN THE |
| MEANS OF EGRESS SHALL BE EITHER BY A RAMP OR A STAIR. |
| THE PRESENCE AND LOCATION OF RAMPED WALKWAYS SHALL BE |
| READILY APPARENT. |
| |
| 4B) 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS |
| NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A |
| STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE |
| 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF |
| EACH STEP SHALL BE READILY APPARENT. NOT SHOWN ON |
| PLANS. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |