2011-07-13 13:01:02****CORRECTIONS****
 11070054
  
 1. DETAIL 5 SHEET M2 NOT COMPLETE; ATTACHMENT TO
 STRUCTURE NOT SPECIFIED (STATES EXTEND TO STRUCTURE.
 REFER TO DETAIL). PLEASE PROVIDE NEW DETAIL OR REVISE
 EXISTING DETAIL, FBC MECHANICAL 302.
  
 2. M1, PLAN NOTE 1 STATES THAT CONDENSATE WILL BE
 DIRECTED TO MOP SINK. SEE WPB MUNICIPAL CODE 90 25, FBC
 MECHANICAL 307.2.1, THIS IS PROHIBITED. PLEASE REVISE.
  
 3. SHOW COMPLIANCE WITH FBC MECHANICAL 606.2.2 DUCT
 SMOKE DETECTORS.
  
 4. PLEASE REVISE PLAN TO SHOW COMPLIANCE WITH FBC
 MECHANICAL 606.4, FAN SHUTDOWN.
  
 5. PLEASE REVISE PLAN TO SHOW COMPLIANCE WITH FBC
 MECHANICAL 606.4.1 AND CLARIFY JOB CONDITIONS.
 MECHANICAL NOTES REFER TO ALARM SYSTEM BUT SHEET CS
 INCLUDES A NOTE WHICH STATES THAT THIS TENANT DOES NOT
 HAVE A FIRE ALARM SYSTEM.
  
 6. THE CFM STATED ON THE FLOOR PLAN DO NOT APPEAR TO BE
 CONSISTENT WITH THE ASHRAE SCHEDULE ON M2. PLEASE CHECK
 AND REVISE AS NECESSARY.
  
 7. OUTSIDE AIR DUCT SHOWN ON PLAN NOTE 3 REQUIRES A
 DAMPER, FBC 13.409.AB.3.3.
  
 8. PROVIDE A STRUCTURAL INSTALLATION DETAIL FOR ROOFTOP
 EQUIPMENT, FBC M 301.12.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER