Plan Review Notes
Plan Review Notes For Permit 11070054
Permit Number 11070054
Review Stop B
Sequence Number 1
Notes
Date Text
2011-07-11 08:31:37BUILDING PLAN REVIEW
 PERMIT: 11070054
 ADD: 771 VILLAGE BLVD SUITE 212-213
 CONT: TO BE DETERMINED
 TEL: (954)583-9990
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO SIGN ONTO PERMIT APPLICATION BEFORE
 ISSANCE, VERIFY LICENSURE AND INSURANCE.
  
 2) SHEET A1 NOTE #8 INDICATES THE WATER HEATER TO BE
 INSTALLED OVER THE RESTROOM CEILING, PLEASE SEE SHEET
 A2.1 DETAIL # 7 INDICATES TTHE WATER HEATER LOCATION TO
 BE OVER THE JANITORS CLOSET, EVEN THE PLUMBING SHEET
 P-3 THE TWO ISOMETRICS INDICATE THE WATER HEATER IN TWO
 LOCATIONS.
  
 3) PLEASE ALSO PROVIDE ADDITIONAL DETAILS FOR POINT
 LOADING OF THE BAR JOIST:
 3A) IF THE LOCATION OF TTHE WATER HEATER IS OVER THE
 JANITORS CLOSET THE BAR JOIST BOTTOM CHORD USALLY DOES
 NOT CONTINUE TO THE BEARING WALL AND BRIDGING IS USALLY
 WELDED ONTO THE BOTTOM CHORD, IF THIS CONDITION EXIST
 HOW WILL THE HEATER BE HUNG FROM BAR JOIST.
  
 3B) IF THE LOCATION OF THE WATER HEATER IS LOCATED OVER
 THE RESTROOM PLEASE LOCATE ON PLANS?
  
 4) SHEET A2.1 NOTE #1 INDICATES THE STOREFRONT TO BE
 REMOVED AND NEW SYSTEM TO INSTALLED:
  
 4A) MISSING WIND DESIGN, 1609.6.2 WIND DESIGN
 PROCEDURES
 4A)1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 4A) 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 4A) 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4A) 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 4A) 5) PRESSURES +/-.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 1) STOREFRONT DOOR
  
 2) STOREFRONT GLAZING
  
 3) STORM SHUTTERS IF LARGE MISSILE IMPACT RESISTANT
 TESTED GLAZING SYSTEMS IS NOT INSTALLED.
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) SHEET A2.1 NOTE NOTE # 2 INDICATEES PEIR TO BE
 REPLACED, PLEASE PROVIDE DETAILS TO WHAT IS THE
 STRUCTURAL BASE OF THIS PIER AND WHAT WILL BE ADDED TO
 THIS PIER FOR THE WINDOW FRAME TO ATTACH TO FOR
 ANCHORING. 2007/ 09 FBC-B 1609 WIND LOADING AND PART OF
 THE MWFRS.
  
 JAMES A. WITMER C.B.O.
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  