2011-07-11 08:31:37 | BUILDING PLAN REVIEW |
| PERMIT: 11070054 |
| ADD: 771 VILLAGE BLVD SUITE 212-213 |
| CONT: TO BE DETERMINED |
| TEL: (954)583-9990 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) CONTRACTOR TO SIGN ONTO PERMIT APPLICATION BEFORE |
| ISSANCE, VERIFY LICENSURE AND INSURANCE. |
| |
| 2) SHEET A1 NOTE #8 INDICATES THE WATER HEATER TO BE |
| INSTALLED OVER THE RESTROOM CEILING, PLEASE SEE SHEET |
| A2.1 DETAIL # 7 INDICATES TTHE WATER HEATER LOCATION TO |
| BE OVER THE JANITORS CLOSET, EVEN THE PLUMBING SHEET |
| P-3 THE TWO ISOMETRICS INDICATE THE WATER HEATER IN TWO |
| LOCATIONS. |
| |
| 3) PLEASE ALSO PROVIDE ADDITIONAL DETAILS FOR POINT |
| LOADING OF THE BAR JOIST: |
| 3A) IF THE LOCATION OF TTHE WATER HEATER IS OVER THE |
| JANITORS CLOSET THE BAR JOIST BOTTOM CHORD USALLY DOES |
| NOT CONTINUE TO THE BEARING WALL AND BRIDGING IS USALLY |
| WELDED ONTO THE BOTTOM CHORD, IF THIS CONDITION EXIST |
| HOW WILL THE HEATER BE HUNG FROM BAR JOIST. |
| |
| 3B) IF THE LOCATION OF THE WATER HEATER IS LOCATED OVER |
| THE RESTROOM PLEASE LOCATE ON PLANS? |
| |
| 4) SHEET A2.1 NOTE #1 INDICATES THE STOREFRONT TO BE |
| REMOVED AND NEW SYSTEM TO INSTALLED: |
| |
| 4A) MISSING WIND DESIGN, 1609.6.2 WIND DESIGN |
| PROCEDURES |
| 4A)1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| |
| 4A) 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION1609.5. |
| |
| 4A) 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4. |
| |
| 4A) 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| |
| 4A) 5) PRESSURES +/-. |
| |
| 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 1) STOREFRONT DOOR |
| |
| 2) STOREFRONT GLAZING |
| |
| 3) STORM SHUTTERS IF LARGE MISSILE IMPACT RESISTANT |
| TESTED GLAZING SYSTEMS IS NOT INSTALLED. |
| |
| 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 7) SHEET A2.1 NOTE NOTE # 2 INDICATEES PEIR TO BE |
| REPLACED, PLEASE PROVIDE DETAILS TO WHAT IS THE |
| STRUCTURAL BASE OF THIS PIER AND WHAT WILL BE ADDED TO |
| THIS PIER FOR THE WINDOW FRAME TO ATTACH TO FOR |
| ANCHORING. 2007/ 09 FBC-B 1609 WIND LOADING AND PART OF |
| THE MWFRS. |
| |
| JAMES A. WITMER C.B.O. |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |