Plan Review Notes For Permit 11060767 |
Permit Number |
11060767 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-06-30 13:39:25 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE COMPLETE PRODUCT APPROVAL AS REQUIRED BY DCA | | RULE 9N-3 FOR: | | A) THE SPECIFIC ROOF TILE TO BE INSTALLED. CONTRACTOR | | ONLY SUBMITTED THE FLORIDA PRODUCT APPROVAL COVER PAGE | | FL7804-R3 BUT IS MISSING THE NOA FOR THE SPECIFIC TILE | | TO BE INSTALLED. | | | | B) POLYFOAM TECHNICAL INFORMATION. CONTRACTOR ONLY | | SUBMITTED THE FLORIDA PRODUCT APPROVAL COVER PAGE | | FL6332-R2, BUT IS MISSING THE TECHNICAL INFORMATION | | SUBMITTED TO GET THE FLORIDA APPROVAL. | | | | 2- SPECIFY SQUARE FOOTAGE OF TILES TO BE INSTALLED TO | | VERIFY COMPLIANCE WITH THE VALUATION DECLARED IN THE | | PERMIT APPLICATION. SEC. 108.3 CITY AMENDMENTS TO FBC. | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|