Plan Review Notes For Permit 11060741
Permit Number 11060741
Review Stop P
Sequence Number 1
Notes
Date Text
2011-06-30 16:30:402009 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 * DUE TO CODE CHANGES AFTER THE ORIGINAL PERMIT WAS
 ISSUED, THE USE OF AN ATMOSPHERIC VENT TO PREVENT
 ENTRAPMENT AT THE DRAINS IS NO LONGER ALLOWED.
  
 1) SUBMIT TWO SETS OF TDH CALCULATIONS FOR THE SYSTEM.
 SUBMIT THE PUMP CURVE FOR THE PUMP SPECIFIED ON THE
 PLANS. WHEN TDH CALCULATIONS ARE NOT SUBMITTED THE
 MAXIMUM FLOW RATE IS USED TO DETERMINE THE WATER
 VELOCITY. AT 75 GPM WITH A 60' TDH THE WATER VELOCITY
 IN 2" PIPE IS 7.66 FEET PER SECOND AND EXCEEDS THE 6
 FEET PER SECOND ALLOWED IN THE BRANCH SUCTION PIPING AT
 THE TWO MAIN DRAINS. SEE ANSI/APSP 7 4.4. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]