2011-06-29 14:46:50RESIDENTIAL (R3) SHUTTERS INSTALLATION BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDION SHUTTER SPAN FOR OPENING #12 EXCEEDS THE
 MAXIMUM PANEL SPAN OF 13'-0". SEE TABLE 3 ON SHUTTERS
 DRAWINGS. PROVIDE PRODUCT APPROVAL THAT ALLOWS THE SPAN
 SPECIFIED FOR OPENING #12 AS REQUIRED BY DCA RULE
 9B-72.
  
 2- ACCORDING TO TABLE 3 ON SHEET 1 OF 22 OF ACCORDION
 SHUTTERS FLORIDA PRODUCT APPROVAL FL10753-R3 SUBMITTED
 THE MAXIMUM SHUTTER SPAN IS 142". SHUTTER SPAN FOR
 OPENINGS #10, #11, #12 AND #14 NEED TO BE REVISED.
 NOTE: TABLE 3 IS BASED ON THE CALCULATED DESIGN
 PRESSURES. CONTRACTOR WROTE ON FRONT PAGE OF THE
 INSTALLATION SCHEDULE WORST CASE DESIGN PRESSURES OF
 62PSF. THIS WERE THE DESIGN PRESSURES USED TO CHECK THE
 MAXIMUM SPAN.
  
 3- CLARIFY HOW OPENING #10 COMPLIES WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.4.
  
 4- DESIGN PRESSURES SUBMITTED FROM ENGINEERING EXPRESS
 NEED TO HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL
 AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 5- COORDINATE INFORMATION SHOWN ON THE SHUTTERS
 INSTALLATION WITH ENGINEER CALCULATIONS AND WITH WORST
 CASE DESIGN PRESSURES SPECIFIED ON FRONT OF
 INSTALLATION SCHEDULE.
  
 6- CLEARLY IDENTIFY SPECIFIC ACCORDION SHUTTERS
 MOUNTING SECTION AND CONNECTION TYPE. EG: BUILD OUT
 MOUNT SECTION CA, WALL MOUNT SECTION D OR DECORATIVE
 FLOOR TRACK DETAIL N. ALL OF THEM ARE CIRCLED ON THE
 PRODUCT APPROVAL SUBMITTED. NEED TO IDENTIFY SPECIFIC
 ONE THAT APPLIES TO THIS JOB TO VERIFY CONNECTION TYPE
 SPECIFIED. SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 7- ANCHOR SPECIFIED ON INSTALLATION SCHEDULE DOESN'T
 PROVIDE THE 1 3/4" MIN. EMBEDMENT IN CONCRETE AS
 REQUIRED ON THE ANCHOR SCHEDULE FOR CONCRETE. REVISE
 THE 2 1/4" ANCHOR SPECIFIED ON THE INSTALLATION
 SCHEDULE AND CLEARLY SPECIFY TYPE OF TAPCON. SEE ANCHOR
 TABLE FOR CONCRETE. NOTE: EMBEDMENT DOESN'T INCLUDE THE
 5/8" STUCCO FINISH AND THE THICKNESS OF THE SHUTTERS
 TRACK.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712