Plan Review Notes
Plan Review Notes For Permit 11060684
Permit Number 11060684
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-06-29 09:12:555312 BROADWAY
 TRACKING #11060684
 PERMIT #10120531
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ELEVATOR RECALL IS NOT REQUIRED; HOWEVER, A HEAT
 DETECTOR OR FLOW SWITCH WITHOUT TIME DELAY IS NEEDED TO
 SHUNT TRIP POWER TO THE ELEVATOR PRIOR TO SPRINKLER
 ACTIVATION IN THE ELEVATOR MACHINE ROOM.
  
 FIRE ALARM NOTES #14: DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION PER LOCAL CODE
 AMENDMENTS.
  
 VOICE EVACUATION MESSAGE SHALL STATE AN EMERGENCY HAS
 BEEN REPORTED AND ALL OCCUPANTS ARE TO LOCATE THE
 NEAREST EXIT AND EVACUATE THE BUILDING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE