Plan Review Notes For Permit 11060676 |
Permit Number |
11060676 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-06-30 11:52:45 | 2381 PALM BEACH LAKES BOULEVARD | | PERMIT #11060676 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO***** | | | | PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING | | OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE | | EXTINGUISHER COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS | | SHALL NOT EXCEED 75 FEET. | | | | THE EXISTING EXIT SIGNS IN ROOM #104 AND #116 CANNOT BE | | SEEN BY OCCUPANTS IN ROOM #109 OR #112. PROVIDE | | ADDITIONAL EXIT SIGNS. | | | | PROVIDE TACTILE SIGNAGE AT EXIT DOORS. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|