Plan Review Notes
Plan Review Notes For Permit 11060656
Permit Number 11060656
Review Stop P
Sequence Number 1
Notes
Date Text
2011-07-15 08:47:012007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE TDH CALCULATIONS ON SHEET 2 OF THE PLANS INCLUDE
 A POOL HEATER AND THE APPLICATION SPECIFIES NO POOL
 HEATER. WHEN THE TDH OF 18 IS REMOVED FROM THE
 CALCULATIONS THE TOTAL TDH IS 28.8. USING THE PUMP
 CURVE FOR THE 1 HP PENTAIR WHISPERFLO POOL PUMP THE
 FLOW RATE IS 110 GPM WITH A TDH OF 28.8. THE VELOCITY
 IN THE 2.5 " SUCTION LINES WILL BE 7.18 FT/SEC, WHICH
 IS ACCEPTABLE. HOWEVER, THE VELOCITY IN THE 2" RETURN
 PIPING IS 11.23 FT/SEC, WHICH EXCEEDS THE 10 FT/SEC
 ALLOWED BY FBC R4101.6.3. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]